Global commands, Global commands -21 – Basler Electric BE1-700 User Manual
Page 267

S
Purpose:
Read/Set 81 Under Voltage Inhibit level
Syntax:
S{g}-81INH[={pu(V)},{NegSeq(%)},{Over(Hz)},{Under(Hz)}] where g=0,1
Example:
S0-81INH or S0-81INH=80,5,70,40 or S1-81INH=0,7,65,55
Reference:
Section 4, Protection and Control, Frequency Protection
SP-60FL Command (BE1-700V only)
Purpose:
Read/Set 60 Fuse Loss Blocking
Syntax:
SP-60FL[={I_Blk},{V_Blk}] I_Blk=ENA/DIS, V_Blk=DIS/PNQ/PN/PQ/NQ/P/N/Q
Example:
SP-60FL or SP-60FL=ENA,PNQ or SP-60FL=DIS,DIS
Reference:
Section 4, Protection and Control, Voltage Transformer Fuse Loss Detection
SP-BF Command (BE1-700C only)
Purpose:
Read/Set the Breaker Failure Timer Setting
Syntax:
SP-BF[={time}[m/s/c]] where m=msec,s=sec,c=cycle
Example:
SP-BF or SP-BF=50m or SP-BF=3c
Reference:
Section 4, Protection and Control, Breaker Failure Protection
SP-CURVE Command (BE1-700C only)
Purpose:
Read/Set the user programmable 51 curve parameters
Syntax:
SP-CURVE[={A},{B},{C},{N},{R}]
Example:
SP-CURVE or SP-CURVE=1.0,0,0,2.5,0
Reference:
Appendix A, Time Overcurrent Characteristic Curves
SP-GROUP Command
Purpose:
Read/Program auxiliary setting group 1 operation
Syntax:
SP-GROUP[{g}]=[{sw_time},{sw_level},{ret_time},{ret_level},{prot_ele}]
Example:
SP-GROUP, SP-GROUP1=10,75,10,50,51P or SP-GROUP1=0,0,0,0,793
Reference:
Section 4, Protection and Control, Setting Groups
SP-79ZONE Command (Optional)
Purpose:
Read/Set 79 Zone Sequence Logic
Syntax:
SP-79ZONE[={zone pickup logic}]
Example:
SP-79ZONE or SP-79ZONE=50TPPU+50TNPU
Reference:
Section 4, Protection and Control, Reclosing
Global Commands
GS-PW Command
Purpose:
Read/Set Password and password access port(s)
Syntax:
GS-PW[{t}[={password},{com ports(0/1/2)}]] where t=G/S/C/R
Example:
GS-PWG=TEST,0 or GS-PWS=XYZ,1/2
Reference:
Section 9, Security
9376700990 Rev M
BE1-700 ASCII Command Interface
11-21