Control commands, Report commands, Control commands -10 – Basler Electric BE1-700 User Manual
Page 256: Report commands -10

M-SYNC Command
Purpose:
Read metered sync angle between Phase & Aux inputs
Syntax:
M-SYNC
Example:
M-SYNC or M-SYN
Reference:
Section 5, Metering
M-V Command
Purpose:
Read metered voltage (V) in primary units
Syntax:
M-V[{phase}] where phase = A/B/C/AB/BC/CA/2
Example:
M-V or M-VA or M-VAB or M-V2
Reference:
Section 5, Metering
Control Commands
CO Command
Purpose:
Control Operation
Syntax:
CO-{control}[={mode}] where control=GROUP/OUT/x43/101
mode=0-1/L for GROUP, 0/1/P/L/ENA/DIS for OUT,
0/1/P for x43 and T/C for 101.
Example:
CO-GROUP=1 or CO-OUT1=1 or CO-43=P
Reference:
Section 3, Input and Output Functions, Outputs
Section 4, Protection and Control, Setting Groups
Section 4, Protection and Control, Virtual Switches
CS Command
Purpose:
Control Selection
Syntax:
CS-control[={mode}] where control=GROUP/OUT/x43/101
mode=0-1/L for GROUP, 0/1/P/L/ENA/DIS for OUT,
0/1/P for x43 and T/C for 101.
Example:
CS-GROUP=1 or CS-OUT1=1 or CS-43=P
Reference:
Section 3, Input and Output Functions, Outputs
Section 4, Protection and Control, Setting Groups
Section 4, Protection and Control, Virtual Switches
Report Commands
RA Command
Purpose:
Report/Reset Alarm information
Syntax:
RA[=0]
Example:
RA
Reference:
Section 6, Reporting and Alarm Functions, Alarms Function
RA-LGC Command
Purpose:
Report/Reset Logic Alarm information
Syntax:
RA-LGC[=0]
Example:
RA-LGC
Reference:
Section 6, Reporting and Alarm Functions, Alarms Function
RA-MAJ Command
Purpose:
Report/Reset Major Alarm information
Syntax:
RA-MAJ[=0]
Example:
RA-MAJ
Reference:
Section 6, Reporting and Alarm Functions, Alarms Function
11-10
BE1-700 ASCII Command Interface
9376700990 Rev M