59x auxiliary overvoltage protection (be1-700v), 60fl fuse loss (be1-700v), 62 logic timers – Basler Electric BE1-700 User Manual
Page 22: 79 recloser protection, 81 over/under frequency protection (be1-700v), Automatic setting group characteristics, 60fl fuse loss (be1-700v) -10, 62 logic timers -10, 79 recloser protection -10, 81 over/under frequency protection (be1-700v) -10

59X Auxiliary Overvoltage Protection (BE1-700V)
Pickup
Setting Range:
1 to 150 V
Accuracy:
±2% of setting or ±1 V, whichever is greater
Dropout/Pickup Ratio:
98%
Time Delay
Setting Range:
0.050 to 600 s
Accuracy:
±0.5% or ±2.5 cycles, whichever is greater
60FL Fuse Loss (BE1-700V)
Time Delay:
Fixed at 50 ms
62 Logic Timers
Modes:
Pickup/Dropout, 1 Shot Nonretriggerable, 1 Shot
Retriggerable, Oscillator, Integrating, Latch
Setting Range:
0 to 9,999 s
Accuracy:
±0.5% or ±12 ms, whichever is greater
79 Recloser Protection
Reclose (791, 792, 793, 794), Reset (79R), Max Cycle (79M), Reclose Fail (79F), Pilot (79P)
Setting Range:
100 ms to 600 s
Accuracy:
±0.5% or +1¾, –0 cycles, whichever is greater
81 Over/Under Frequency Protection (BE1-700V)
Pickup
Setting Range:
20 to 70 Hz
Accuracy:
±0.01 Hz
Dropout :
0.02 Hz
±0.01 Hz of the actual pickup value
Time Delay
Setting Range:
0.00 to 600 s
Accuracy:
±0.5% or ±1 cycle, whichever is greater, plus 3
cycle recognition time
Voltage Inhibit
Setting Range:
15 to 300 V
Accuracy:
±2% or ±1 V, whichever is greater
Automatic Setting Group Characteristics
Number of Setting Groups:
2
Control Modes
Automatic:
Cold-Load Pickup, Dynamic Load or Unbalance,
Recloser Shot, or Unbalance (BE1-700C); Fuse
Loss (60FL) (BE1-700V)
External:
Discrete Input Logic, Binary Input Logic
Switch Level
Setting Range:
0 to 150% of the Setting Group 0, monitored
element setting
Accuracy:
±2% or ±50 mA (5 A), ±2% or ±10 mA (1 A)
Switch Timer
Setting Range:
0 to 60 min with 1 min increments where 0 =
disabled
Accuracy:
±0.5% or ±2 s, whichever is greater
1-10
BE1-700 General Information
9376700990 Rev M