Basler Electric BE1-700 User Manual
Page 188
Function
Purpose
BESTlogic
Expression
Mode Setting
50TQ
Used for instantaneous negative-sequence overcurrent
protection.
0
1 (enabled)
150TP
Not used
0
0 (disabled)
150TN
Not used
0
0 (disabled)
150TQ
Not used
0
0 (disabled)
51P
Used for timed phase-overcurrent protection.
0
1 (enabled)
51N
Used for timed neutral-overcurrent protection
0
1 (3-phase
Residual)
51Q
Used for timed negative-sequence overcurrent protection.
0
1 (enabled)
151N
Not used
0
0 (disabled)
62
Not used
0
0 (disabled)
162
Not used
0
0 (disabled)
BF
Not used
0
0 (disabled)
GROUP
Input 0 Logic: No manual selection logic is used.
0
1
(discrete input
selection)
Input 1 Logic: No manual selection logic is used.
0
Auto/Manual Logic: Set to 1 (/0) to enable automatic
selection. No manual selection is used.
/0
Table 8-3. 700C-5051-A-BE (Basic OC) Virtual Switch Logic
Switch
Purpose
Mode
Label
State Labels
TRUE
FALSE
43
Not used
0 (disabled)
SWITCH_43
CLOSED
OPEN
143
Not used
0 (disabled)
SWITCH_143
CLOSED
OPEN
8-6
BE1-700 Application
9376700990 Rev M