Table 13-15. 50tq/150tq pickup values -18, Table 13-16. 150tq pickup test commands -18 – Basler Electric BE1-700 User Manual
Page 314

Step 4: Slowly ramp up A-phase current until OUT1 closes. Verify that pickup occurred within the
specified accuracy of the relay (5 A sensing:
±3 percent or ±75 mA, 1 A sensing: ±3 percent or
Table 13-15 provides the upper and lower limits for the specified tests.
Table 13-15. 50TQ/150TQ Pickup Values
Sensing Type
Pickup Setting
Lower Limit
Upper Limit
1 A
S0-50TQ=0.1,0
0.225 Aac
0.375 Aac
S0-50TQ=1.0,0
2.91 Aac
3.09 Aac
S0-50TQ=5.0,0
14.55 Aac
15.45 Aac
5 A
S0-50TQ=0.5,0
1.425 Aac
1.575 Aac
S0-50TQ=5.0,0
14.55 Aac
15.45 Aac
S0-50TQ=10.0,0
29.1 Aac
30.1 Aac
Step 5: After pickup occurs, slowly ramp the current down until OUT1 opens. Verify that dropout
occurred as specified (95 percent,
±2 percent). Verify 50TQ target on the HMI.
Step 6: Repeat Steps 3, 4, and 5, applying all Table 13-15 values that apply to your sensing input type.
Step 7: (Optional.) Repeat Steps 3 through 6 for phase B (Terminals D3 and D4) and phase C
(Terminals D5 and D6).
Step 8: (Optional.) Repeat Steps 1 through 7 for the 150TQ elements. Use Table 13-16 as a reference
when substituting the commands used in Step 1.
Table 13-16. 150TQ Pickup Test Commands
Replace These Commands
With These Commands
SL-50TQ=1,0
SL-150TQ=1,0
SL-VO1=50TQT
SL-VO1=150TQT
SG-TRIG=50TQT,50TQPU,0
SG-TRIG=150TQT,150TQPU,0
SG-TARG=50TQ
SG-TARG=150TG
Step 9: (Optional.) Repeat Steps 1 through 8 for the 50TQ and 150TQ elements in Setting Group 1.
50TQ/150TQ Time Delay Verification
Step 1: Connect a current source to Terminals D1 and D2 (A-phase).
Step 2: Prepare the 50TQ and 150TQ elements for testing by transmitting the commands in Table
13-17 to the relay.
Table 13-17. 50TQ/150TQ Time Delay Test Commands
Command
Purpose
A=
Gains write access.
SL-N=NONE
Zero out custom settings. Overwrite with LOGIC=NONE settings.
Y
Confirm overwrite.
SL-N=Q50
Sets Q50 as custom logic name.
SL-50TQ=1,0
Enables 50TQ, disables blocking.
SL-150TQ=1,0
Enables 150TQ, disables blocking.
SL-VO1=50TQT
Enables OUT1 to close for 50TQ trip.
SL-VO2=150TQT
Enables OUT2 to close for 150TQ trip.
13-18
BE1-700 Testing and Maintenance
9376700990 Rev M