Basler Electric BE1-700 User Manual
Page 257

RA-MIN Command
Purpose:
Report/Reset Minor Alarm information
Syntax:
RA-MIN[=0]
Example:
RA-MIN
Reference:
Section 6, Reporting and Alarm Functions, Alarms Function
RA-REL Command
Purpose:
Report/Reset Relay Alarm information
Syntax:
RA-REL[=0]
Example:
RA-REL
Reference:
Section 6, Reporting and Alarm Functions, Alarms Function
RB Command
Purpose:
Read breaker status
Syntax:
RB
Example:
RB
Reference:
Section 6, Reporting and Alarm Functions, Breaker Monitoring
RB-DUTY Command
Purpose:
Read/Set breaker contact Duty Log
Syntax:
RB-DUTY[{phase}[={%duty}]] where %duty is % of dmax set with SB-DUTY
Example:
RB-DUTYA or RB-DUTYB=50
Reference:
Section 6, Reporting and Alarm Functions, Breaker Monitoring
RB-OPCNTR Command
Purpose:
Read/Set Breaker Operation Counter
Syntax:
RB-OPCNTR[={#operations}]
Example:
RB-OPCNTR=32 or RB-OPCNTR=652
Reference:
Section 6, Reporting and Alarm Functions, Breaker Monitoring
RD Command (BE1-700C only)
Purpose:
Report all demand data
Syntax:
RD
Example:
RD
Reference:
Section 6, Reporting and Alarm Functions, Demand Functions
RD-PI Command
Purpose:
Read/Reset peak demand current (I)
Syntax:
RD-PI[{p}[=0]] where p=A/B/C/N/Q
Example:
RD-PI or RD-PIA or RD-PIN or RD-PI=0
Reference:
Section 6, Reporting and Alarm Functions, Demand Functions
RD-TI Command
Purpose:
Report today's demand current (I)
Syntax:
RD-TI[{p}] where p=A/B/C/N/Q
Example:
RD-TI or RD-TIA or RD-TIN
Reference:
Section 6, Reporting and Alarm Functions, Demand Functions
RD-YI Command
Purpose:
Report yesterday's demand current (I)
Syntax:
RD-YI[{p}] where p=A/B/C/N/Q
Example:
RD-YI or RD-YIA or RD-YIN
Reference:
Section 6, Reporting and Alarm Functions, Demand Functions
9376700990 Rev M
BE1-700 ASCII Command Interface
11-11