Command summary, Miscellaneous commands, Metering commands – Basler Electric BE1-700 User Manual
Page 255: Command summary -9, Miscellaneous commands -9, Metering commands -9

SG-COM0=1200,P24,R1,X1
SG-COM2=19K,A156,P0,R1,X0
COMMAND SUMMARY
Miscellaneous Commands
ACCESS Command
Purpose:
Read/Set Access level in order to change settings
Syntax:
ACCESS[={password}]
Example:
ACCESS=700
Reference:
Section 11, ASCII Command Interface, Miscellaneous Command Descriptions
EXIT Command
Purpose:
Exit programming mode
Syntax:
EXIT
Note: Relay will prompt for verification
Example:
EXIT
Reference:
Section 11, ASCII Command Interface, Miscellaneous Command Descriptions
HELP Command
Purpose:
Obtain help on command operation
Syntax:
HELP {cmd} or H {cmd} for help on {cmd}, H1 for command list
Example:
HELP, H1, H SG-COM
Reference:
Section 11, ASCII Command Interface, Miscellaneous Command Descriptions
Metering Commands
M Command
Purpose:
Read all metered values
Syntax:
M
Example:
M
Reference:
Section 5, Metering
M-3V0 Command
Purpose:
Read metered voltage (V) in primary units
Syntax:
M-3V0
Example:
M-3V0
Reference:
Section 5, Metering
M-FAST Command
Purpose:
Read fast metered values in primary units
Syntax:
M-FAST[{xy}] where x=V,I,F,P,Q,S and y=P,L,S,1,2,3,4,G
Example:
M-FAST,V or M-FAST,VP or M-FAST,I or M-FAST,L1
Reference:
Section 5, Metering
M-FREQ Command
Purpose:
Read metered frequency (F)
Syntax:
M-FREQ[{source}] where source = P/X/S, Phase, Aux, Slip
Example:
M-F or M-FREQ, M-FREQP, M-FREQX, M-FREQS
Reference:
Section 5, Metering
M-I Command
Purpose:
Read metered current (I) in primary units
Syntax:
M-I[{phase}] where phase = A/B/C/N/Q/G
Example:
M-I or M-IA or M-IG
Reference:
Section 5, Metering
9376700990 Rev M
BE1-700 ASCII Command Interface
11-9