Basler Electric BE1-700 User Manual
Page 266

S
Purpose:
Read/Set 47 pickup level and time delay
Syntax:
S{g}-47[={pu(V)},{td(m)}] where g=0,1
Example:
S0-47 or S1-47=100,0
Reference:
Section 4, Protection and Control, Voltage Protection
S
Purpose:
Read/Set 50T pickup level and time delay
Syntax:
S{g}-{x}50T[{p}][={pu(A)},{td(m)}] where g=0,1, x=blank/1, and p=P/N/Q
Example:
S0-50T or S1-50TP=25,0 or S1-150TN=3,20
Reference:
Section 4, Protection and Control, Overcurrent Protection
S
Purpose:
Read/Set 51 pickup level, time delay, curve, and direction
Syntax:
S{g}-51[{p}][={pu(A)},{td(m)},{crv},{dir}] where g=0,1 and p=P/Q
Example:
S0-51P or S0-51P=7.5,6.5,S1,N or S1-51Q=3,2.0,S1,F
Reference:
Section 4, Protection and Control, Overcurrent Protection
S
Purpose:
Read/Set 51N pickup level, time delay and curve
Syntax:
S{g}-{x}51N[={pu(A)},{td(m)},{crv},{dir}] where x=blank/1 and g=0,1
Example:
S0-51N or S0-51N=7.5,6.5,S1,N or S1-151N=3,2.0,S1,F
Reference:
Section 4, Protection and Control, Overcurrent Protection
S
Purpose:
Read/Set 59 pickup level and time delay
Syntax:
S{g}-59[{p}][={pu(V)},{td(m)}] where g=0,1 and p=P/X
Example:
S0-59P or S1-59P=100,0 or S1-59X=80,20 S1-159X=80,20
Reference:
Section 4, Protection and Control, Voltage Protection
S
Purpose:
Read/Set 62 Time Delay
Syntax:
S{g}-{x}62[={t1},{t2}] where g=0,1 & t suffix m=msec,s=sec,c=cycle
Example:
S0-62=500m,200m or S0-62=0.5s,0.2s or S1-162=30c,12c
Reference:
Section 4, Protection and Control, General Purpose Logic Timers
S
Purpose:
Read/Set 79 Time Delay
Syntax:
S{g}-79[#][={td}] where g=0,1 & t suffix m=msec,s=sec,c=cy
Example:
S0-791=100m or S0-792=0.5s or S0-793=60c
Reference:
Section 4, Protection and Control, Reclosing
S
Purpose:
Read/Set 79 Sequence Controlled Block Output
Syntax:
S{g}-79SCB[={step list}] where g=0,1
Example:
S0-79SCB=2/4
Reference:
Section 4, Protection and Control, Reclosing
S
Purpose:
Read/Set 81 pickup level, time delay, and mode
Syntax:
S{g}-{x}81[={pu(Hz)},{td(m)},{mode}] where g=0,1 and x=blank/1/2/3/4/5
Example:
S0-81 or S0-81=59.00,6.5,U or S1-81=60.50,2.0,O or S1-81=0.2,0,R
Reference:
Section 4, Protection and Control, Frequency Protection
11-20
BE1-700 ASCII Command Interface
9376700990 Rev M