Page 18: Metered frequency values and accuracy (be1-700v), Calculated values and accuracy, Operational specifications -6, Metered current values and accuracy (be1-700c) -6, Metered voltage values and accuracy (be1-700v) -6, Calculated values and accuracy -6, Figure 1-1. style number identification chart -6

Figure 1-1. Style Number Identification Chart
OPERATIONAL SPECIFICATIONS
Depending on the style ordered, BE1-700 relays have the following features and capabilities:
Metered Current Values and Accuracy (BE1-700C)
Current Range
5 Aac Nominal:
0.5 to 15 Aac
1 Aac Nominal:
0.1 to 3.0 Aac
Accuracy:
±1% of reading, ±1 least significant digit at 25°C
Temperature Dependence:
≤ ±0.02% per °C
Metered Voltage Values and Accuracy (BE1-700V)
Voltage Range
3-wire:
0 to 300 V
L-L
4-wire:
0 to 300 V
L-L
Accuracy (10 to 75 hertz)
50 V to 300 V:
±0.5% of reading, ±1 least significant digit at 25°C
Temperature Dependence:
≤ ±0.02% per °C
Metered Frequency Values and Accuracy (BE1-700V)
Frequency Range:
10 to 75 Hz
Accuracy:
±0.01 hertz, ±1 least significant digit at 25°C
Sensing Input
3-wire:
Phase A – B
4-wire:
Phase A – Neutral
Minimum Frequency Tracking Voltage:
10 V rms
Calculated Values and Accuracy
Demand
Range:
0.1 to 1.5 nominal
Type:
Exponential
Accuracy:
±1% of reading ±1 digit at 25°C
Temperature Dependence:
≤ ±0.02% per °C
Interval:
1 to 60 min
1-6