Settings (S) Command Descriptions
Reading All Settings
All user programmable settings can be listed using the S command. This read-only command is useful for
documenting relay status during installation. The settings retrieved by the S command can be saved to a
standard text file and sent to another relay to be configured with the same settings. This type of settings
transfer takes less than one minute.
S Command
Purpose:
Read all relay setting parameters
Syntax:
S
Example:
S
The S command returns the values of relay setting parameters in the same form that they are
programmed. It can be used at the end of a programming session to make a record of the relay settings.
If saved in a file, the report can be sent to another BE1-700 that will use the same settings. Because the
report that is created is a set of commands, sending the report to a different relay re-programs that relay
with the settings contained in the S report.
Reading Specific Groups of Settings
While the S command is useful for reading all relay settings, several commands are available to read
specific groups of settings.
SA Command
Purpose:
Read all alarm settings for Major and Minor alarms
Syntax:
SA
Example:
SA
SA Command Example:
Example 1.
Read all alarm settings.
>SA
SA-BKR1=0,0;
SA-BKR2=0,0;
SA-BKR3=0,0
SA-DIP=0.00;
SA-DIN=0.00;
SA-DIQ=0.00
SA-LGC=0
SA-MAJ=25
SA-MIN=29
SA-RESET=0
SB Command
Purpose:
Read all breaker settings
Syntax:
SB
Example:
SB
SB Command Example:
Example 1.
Read all breaker settings.
>SB
SB-DUTY=0,0.000e+00
SB-LOGIC=/IN1
SG Command
Purpose:
Read all general settings
Syntax:
SG
Example:
SG
9376700990 Rev M
BE1-700 ASCII Command Interface
11-5