Basler Electric BE1-700 User Manual
Page 258

RF Command
Purpose:
Read/Reset Fault Report Data
Syntax:
RF[-n/NEW][=0/TRIG] where n=record # or NEW = new records
Example:
RF (displays a directory of all fault reports in memory)
RF-23 (view summary report for fault record 23)
RF-NEW (view summary report for newest fault record since RF=0 reset)
RF=TRIG (Manually Trigger a fault record)
RF=0 (reset NEW fault counter)
Reference:
Section 6, Reporting and Alarm Functions, Fault Reporting
RG Command
Purpose:
Report General information
Syntax:
RG
Example:
RG
Reference:
Section 6, Reporting and Alarm Functions, Clock
Section 6, Reporting and Alarm Functions, Fault Reporting
RG-DATE Command
Purpose:
Report/Set Date
Syntax:
RG-DATE[={M/D/Y}] or RG-DATE[={D-M-Y}]
Example:
RG-DATE=12/31/96 or RG-DATE=31-12-96 (Format set by SG-CLK Command)
Reference:
Section 6, Reporting and Alarm Functions, Clock
RG-STAT Command
Purpose:
Report relay status
Syntax:
RG-STAT
Example:
RG-STAT
Reference:
Section 6, Reporting and Alarm Functions, General Status Reporting
RG-TARG Command
Purpose:
Report/Reset Target status
Syntax:
RG-TARG
Example:
RG-TARG or RG-TARG=0
Reference:
Section 6, Reporting and Alarm Functions, Fault Reporting
RG-TIME Command
Purpose:
Report/Set Time
Syntax:
RG-TIME[=hr:mn:sc] or RG-TIME[=hr:mn{f}sc]]
Example:
RG-TIME=13:25:00 or RG-TIME=1:25P00 (Format(f) set by SG-CLK Command)
Reference:
Section 6, Reporting and Alarm Functions, Clock
RG-VER Command
Purpose:
Read Model #, Style #, Program Version, Serial #
Syntax:
RG-VER
Example:
RG-VER
Reference:
Section 6, Reporting and Alarm Functions, Hardware and Software Version Reporting
RO Command
Purpose:
Read Oscillographic COMTRADE .DAT/.CFG/.HDR Fault Report
Syntax:
RO-nA/B[#].CFG/DAT/HDR where n=report number,A=ASCII/B=BINARY,#=OSC 1/2
Example:
RO-3A1.CFG or RO-3A1.DAT or RO-5B2.CFG or RO-5B2.DAT or RO-5A.HDR
Reference:
Section 6, Reporting and Alarm Functions, Fault Reporting
11-12
BE1-700 ASCII Command Interface
9376700990 Rev M