Basler Electric BE1-700 User Manual
Page 196

Function
Purpose
BESTlogic
Expression
Mode Setting
GROUP
Input 0 Logic: No manual selection logic is used
0
1
(discrete input
selection)
Input 1 Logic: No manual selection logic is used
0
Auto/Manual Logic: Set to 1 (/0) to enable automatic
selection. No manual selection is used.
/0
Table 8-8. 700C-OC79-A-BE (OC with 79) Virtual Switch Logic
Switch
Purpose
Mode
Label
State Labels
TRUE
FALSE
43
Not used
0 (disabled)
SWITCH_43
Closed
Open
143
Not used
0 (disabled)
SWITCH_143
Closed
Open
101
Not used
0 (disabled)
N/A
N/A
N/A
Table 8-9. 700C-OC79-A-BE (OC with 79) Virtual Output Logic
Output
Purpose
Output Description
Label
State Labels
TRUE
FALSE
VOA
(OUTA)
Alarm Output Contact
Alarm contact closes automatically
when relay trouble alarm occurs.
ALARM
Active
Normal
BESTlogic expression: VOA=0
VO1
(OUT1)
Breaker Trip Contact
Contact closes when protective trip
expression is TRUE.
BKR_TRIP
Trip
Normal
BESTlogic expression: VO1=VO11
VO2
(OUT2)
Breaker Close Contact
Close breaker when recloser close
output is TRUE.
BKR_CLOSE
Closed
Normal
BESTlogic expression: VO2=79C
VO3
(OUT3)
Not used
VO3
True
False
BESTlogic expression: VO3=0
VO4
(OUT4)
Minor Alarm
Closes contact when Minor Alarm
expression is TRUE
ALMMIN
Active
Normal
BESTlogic expression: VO4=ALMMIN
8-14
BE1-700 Application
9376700990 Rev M