Figure 6-5. BESTlogic Function Element Screen, Breaker Status
To connect the Breaker Status's CONTROL input, select the CONTROL button. The BESTlogic
Expression Builder screen will open. Select the expression type to be used. Then, select the BESTlogic
variable, or series of variables to be connected to the input. Select Save when finished to return to the
BESTlogic Function Element screen. For more details on the BESTlogic Expression Builder, See Section
7, BESTlogic Programmable Logic. Select Done when the settings have been completely edited.
Table 6-5 lists the settings for the Breaker Status logic.
Table 6-5. Breaker Status Reporting BESTlogic Settings
Setting
Range/Purpose
Default
Breaker Closed Logic
OR logic expression that is TRUE when the
breaker is closed (e.g., 52a logic).
/IN1
Retrieving Breaker Status and Operation Counter Information
Current breaker status can be read from HMI Screen 1.5.6 and through the communication ports using
the RG-STAT command. The General Status Reporting subsection provides more information about this
command.
The number of breaker operations can be read at HMI Screen 4.3.1. The counter value can be adjusted
using the Edit key. This allows the relay counter value to be matched to an existing mechanical
cyclometer on a breaker mechanism. Write access to the reports functions must be gained to edit this
value at the HMI. Breaker operations can be read or set through the communication ports using the RB-
OPCNTR (report breaker, operations counter) command.
The breaker operations counter can be monitored to give an alarm when the value exceeds a threshold.
See Breaker Alarms, in this section for more information about this feature.
Breaker operations can also be read using the RB command. The RB command returns the number of
breaker operations and breaker contact duty information.
Breaker duty monitoring is discussed in the following paragraphs.