Basler Electric BE1-700 User Manual
Page 190

Output
Purpose
Output Description
Label
State Labels
VO8
None
VO8
TRUE
FALSE
BESTlogic Expression: VO8=0
VO9
None
VO9
TRUE
FALSE
BESTlogic Expression: VO9=0
VO10
None
VO10
TRUE
FALSE
BESTlogic Expression: VO10=0
VO11
Protective Trip Expression TRUE when any 50, 150,51 or 151
element times out (trip).
PROT_
TRIP
TRIP
NORMAL
BESTlogic Expression: VO11=50TPT+50TNT+50TQT+150TPT+150TNT+150TQT+51PT+51NT+51QT +151NT
VO12
Protection Picked Up
Expression
TRUE when any 50, 150,51 or 151
element picks up.
PROT_PU
PU
NORMAL
BESTlogic Expression: VO12=50TPPU+50TNPU+50TQPU+150TPPU 150TNPU+150TQPU+51PPU
+51NPU+51QPU+151NPU
VO13
Alarm Mask 21
VO13
TRUE
FALSE
BESTlogic Expression: VO13=0
VO14
Alarm Mask 22
VO14
TRUE
FALSE
BESTlogic Expression: VO14=0
VO15
Alarm Mask 23
VO15
TRUE
FALSE
BESTlogic Expression: VO15=0
Table 8-5. 700C-5051-A-BE (Basic OC) Logic Settings and Equations
SL-N=700C-5051-A-BE
SL-50TP=1,0; SL-50TN=1,0; SL-50TQ=1,0
SL-150TP=0,0; SL-150TN=0,0; SL-150TQ=0,0
SL-51P=1,0
SL-51N=1,0
SL-51Q=1,0
SL-151N=0,0
8-8
BE1-700 Application
9376700990 Rev M