Table 13-13. 50tq pickup test commands -17, Table 13-14. 50tq pickup settings -17 – Basler Electric BE1-700 User Manual
Page 313
Command
Purpose
150TPPU+150TNPU,0
EXIT;Y
Exit and save settings.
Step 8: (Optional.) Repeat Steps 1 through 7 for the 50T and 150T elements in Setting Group 1. Before
testing settings in other setting groups, a setting group must be selected using the CS/CO-
GROUP commands. To activate Setting Group 1, CS-GROUP=1 would be entered to select
Setting Group 1 and CO-GROUP=1 would be entered to make Setting Group 1 active.
In addition, the pickup settings made in Step 3 (Table 13-11) must be changed to specify the
setting group being tested. To test settings in Group 1, replace the 0 in the S0-x50 commands
with a 1 (S1-x50).
50TQ/150TQ Pickup and Dropout Verification
Purpose: To verify the operation of the 50TQ and 150TQ elements.
Reference Commands: SL-50T/150T
Step 1: Connect a current source to Terminals D1 and D2 (A-phase).
Step 2: Prepare the 50TQ and 150TQ elements for testing by transmitting the commands in Table
13-13 to the relay. Reset targets.
Table 13-13. 50TQ Pickup Test Commands
Command
Purpose
A=
Gains write access.
SL-N=NONE
Zero out custom settings. Overwrite with LOGIC=NONE settings.
Y
Confirm overwrite.
SL-N=Q50
Sets Q50 as custom logic name.
SL-50TQ=1,0
Enables 50TQ, disables blocking.
SL-VO1=50TQT
Enables OUT1 to close for 50TQ trip.
SG-CT=1
Sets CT ratio at 1.
SG-TRIGGER=50TQT,50TQPU,0 Enable 50TQT to log and trigger fault recording.
SG-TARG=50TQ
Enables 50TQ targets.
EXIT;Y
Exit and save settings.
Step 3: Using Table 13-14, transmit the first row of setting commands for your sensing input type.
Table 13-14. 50TQ Pickup Settings
Sensing Type
Command
Purpose
1 A
S0-50TQ=0.1,0,N
Sets 50TQ pickup at 0.1 A, TD = 0, non-directional.
S0-50TQ=1.0,0,N
Sets 50TQ pickup at 1.0 A, TD = 0, non-directional.
S0-50TQ=5.0,0,N
Sets 50TQ pickup at 5.0 A, TD = 0, non-directional.
5 A
S0-50TQ=0.5,0,N
Sets 50TQ pickup at 0.5 A, TD = 0, non-directional.
S0-50TQ=5.0,0,N
Sets 50TQ pickup at 0.5 A, TD = 0, non-directional.
S0-50TQ=10.0,0,N
Sets 50TQ pickup at 10.0 A, TD = 0, non-directional.
For a single-phase input test, I
2
= Ia ÷ 3. Therefore, the relay should pick up at a value of three times the
setting value when applying only a single-phase input. For example, to determine the pickup current value
required for an a 1 A relay with a pickup setting of 0.1, it would require 0.1 times 3 or 0.3 amperes of input
current.
9376700990 Rev M
BE1-700 Testing and Maintenance
13-17