Programmable logic setting commands, Programmable logic setting commands -17 – Basler Electric BE1-700 User Manual
Page 263

SG-VTX Command (BE1-700V)
Purpose:
Read/Set Aux VT ratio and connection
Syntax:
SG-VTX[={VTratio},{connection}]
Example:
SG-VTX or VTX=10,AB or VTX=1200:120,GR or VTX=1200/120,AN
Reference:
Section 3, Input and Output Functions, Power System Inputs
Programmable Logic Setting Commands
SL Command
Purpose:
Obtain Setting Logic Information
Syntax:
SL:[{name}]
Example:
SL, SL: or SL:BASIC-OC
Reference:
Section 11, ASCII Command Interface, Settings (S) Command Descriptions
SL-24 Command (BE1-700V only)
Purpose:
Read/Set Logic for 24 Function Modules
Syntax:
SL-24[={mode},{BLK logic}]
Example:
SL-24 or SL-24=1,0 or SL-24=1,IN3
Reference:
Section 4, Protection and Control, Voltage Protection
SL-25 Command (BE1-700V only) (Optional)
Purpose:
Read/Set Logic for 25 Function Modules
Syntax:
SL-25[={mode},{BLK logic}]
Example:
SL-25 or SL-25=1,0 or SL-25=1,IN3
Reference:
Section 4, Protection and Control, Synchronism-Check Protection
SL-27 Command (BE1-700V only)
Purpose:
Read/Set Logic for 27 Function Modules
Syntax:
SL-{x}27[{p}[={mode},{BLK logic}]] where x=blank/1, p=P/X
Example:
SL-27 or SL-27P=1,0 or SL-27X=3,0 or SL-127P=1,IN3
Reference:
Section 4, Protection and Control, Voltage Protection
SL-43 Command
Purpose:
Read/Set Logic for Virtual switch (x43)
Syntax:
SL-{x}43[=mode] where x = blank/1/2/3, mode=0/1/2/3
Example:
SL-43 or SL-43=0 or SL-143=1
Reference:
Section 4, Protection and Control, Virtual Switches
SL-47 Command (BE1-700V only)
Purpose:
Read/Set Logic for 47 Function Modules
Syntax:
SL-47[={mode},{BLK logic}]
Example:
SL-47 or SL-47=1,0 or SL-47=1,IN3
Reference:
Section 4, Protection and Control, Voltage Protection
SL-50T Command (BE1-700C only)
Purpose:
Read/Set Logic for x50 Function Modules
Syntax:
SL-{x}50T[{p}[={mode},{BLK logic}]] where x = blank/1 and p = P/N/Q
Example:
SL-50T or SL-50T=1,0 or SL-150TN=1,IN3
Reference:
Section 4, Protection and Control, Overcurrent Protection
SL-51 Command (BE1-700C only)
Purpose:
Read/Set Logic for 51 Function Modules
Syntax:
SL-51[{p}[={mode},{BLK logic}]] where p=P/N
Example:
SL-51 or SL-51P=1,0 or SL-51N=1,IN3 or SL-151N=1,0
Reference:
Section 4, Protection and Control, Overcurrent Protection
9376700990 Rev M
BE1-700 ASCII Command Interface
11-17