Basler Electric BE1-700 User Manual
Page 262

SG-IN Command
Purpose:
Read/Set Input recognition/debounce
Syntax:
SG-IN[#[={r(ms)},{db(ms)}]] where ms=1-255msec
Example:
SG-IN or SG-IN3 or SG-IN3=4,16
Reference:
Section 3, Input and Output Functions, Contact Sensing Inputs
SG-NOM Command
Purpose:
Read/Enter power system nominal Voltage & Current
Syntax:
SG-NOM[={Nom Volts},{Nom Amps}]
Example:
SG-NOM or SG-NOM=120,5 or SG-NOM=120,1
Reference:
Section 3, Input and Output Functions, Power System Inputs
SG-OSC Command
Purpose:
Read/Set the number of oscillograph fault records saved
Syntax:
SG-OSC[=6/8/10/12/15/16]
Example:
SG-OSC or SG-OSC=6
Reference:
Section 6, Reporting and Alarm Functions, Oscillographic Records
SG-PHROT Command
Purpose:
Read/Set Phase Rotation setting
Syntax:
SG-PHROT[={phase rotation}] ABC/ACB
Example:
SG-PHROT or SG-PHROT=ABC or SG_PHROT=ACB
Reference:
Section 3, Input and Output Functions, Power System Inputs
SG-SCREEN Command
Purpose:
Read/Set default screen(s)
Syntax:
SG-SCREEN[n][={default screen number}]
Example:
SG-SCREEN or SG-SCREEN1=2.2.1 or SG-SCREEN2=2.2.2
Reference:
Section 10, Human-Machine Interface, Front Panel Display
SG-SGCON Command
Purpose:
Read/Set SGC output on time
Syntax:
SG-SGCON[={time}] where time is in (s)ec
Example:
SG-SGCON or SG-SGCON=1S or SG-SGCON=5S
Reference:
Section 4, Protection and Control, Setting Groups
SG-TARG Command
Purpose:
Report/Enable Target List and Reset Target Logic
Syntax:
SG-TARG[={x/x/..x},{rst TARG logic}] where x=27,47,50,51,59,81,181 etc.
Example:
SG-TARG or SG-TARG=27/50/51N/59/81/281
Reference:
Section 6, Reporting and Alarm Functions, Fault Reporting
SG-TRIGGER Command
Purpose:
Read/Set Trigger logic
Syntax:
SG-TRIGGER[n][={TRIP trigger},{PU trigger},{LOGIC trigger}]
Example:
SG-TRIGGER or SG-TRIGGER=VO1,VO2,IN4
Reference:
Section 6, Reporting and Alarm Functions, Fault Reporting
SG-VTP Command (BE1-700V)
Purpose:
Read/Set VT ratio, connection, 27/59 sensing mode, 51/27R sensing mode
Syntax:
SG-VTP[={VT_ratio},{connection},{27/59mode},{51/27Rmode}]
Example:
SG-VTP or VTP=10,4W,PN,PN or VTP=1200:120,3W,PP,PP or VTP=1200/120,AB
Reference:
Section 3, Input and Output Functions, Power System Inputs
11-16
BE1-700 ASCII Command Interface
9376700990 Rev M