Output contacts, Contact-sensing inputs, Irig – Basler Electric BE1-700 User Manual
Page 24: Output contacts -12, Contact-sensing inputs -12, Irig -12

Frequency Range
Options 1, 2, and 4 only:
40 to 70 Hz
Burden
Options 1, 2, 3, 4, 5:
8 W continuous, 11 W maximum with all outputs
energized
Output Contacts
Make and Carry for Tripping Duty:
30 A for 0.2 seconds per IEEE C37.90;
7 A continuous
Break Resistive or Inductive:
0.3 A at 125 or 250 Vdc (L/R = 0.04 maximum)
Contact-Sensing Inputs
Contact-sensing turn-on voltages and burdens are listed in Table 1-2. Burden values assume nominal
value of input voltage applied.
Table 1-2. Contact-Sensing Turn-On Voltages and Burdens
Style Option
Nominal Input Voltage
Contact-Sensing Turn-On Voltage
*
Burden
xxx1xxx
48 Vdc
26 to 38 Vdc
23 k
Ω
xxx2xxx
125 Vac/dc
69 to 100 Vdc
56 to 97 Vac
53 k
Ω
xxx3xxx
24 Vdc
Approx. 5 Vdc
6 k
Ω
xxx4xxx
250 Vac/dc
138 to 200 Vdc
112 to 194 Vac
123 k
Ω
xxx5xxx
125 Vac/dc †
69 to 100 Vdc
56 to 97 Vac
53 k
Ω
* AC voltage ranges are calculated using the default recognition time (4 ms) and debounce time (16 ms).
† Extended holdup option. See Style Chart in Figure 1-1.
Recognition Time
Programmable ................................................................ 4 to 255 ms
IRIG
Supports IRIG Standard 200-98, Format B002
Input Signal:
Demodulated (dc level-shifted digital signal)
Logic-High Voltage:
3.5 Vdc, minimum
Logic-Low Voltage:
0.5 Vdc, maximum
Input Voltage Range:
±20 Vdc, maximum
Resistance:
Nonlinear, approximately 4 k
Ω at 3.5 Vdc,
approximately 3 k
Ω at 20 Vdc
NOTE
All timing specifications are for the worst-case response. This includes output
contact operate times and standard BESTlogic operation timing but excludes
input debounce timing and non-standard logic configurations. If a non-standard
logic scheme involves feedback, then one or more BESTlogic update rate delays
must be included to calculate the worst-case delay. An example of feedback is
Virtual Outputs driving Function Block Inputs. For more information, see Section
7, BESTlogic Programmable Logic.
1-12
BE1-700 General Information
9376700990 Rev M