Table 8-18. 700V-VF79-A-BE (V & F Protection with Reclosing) Virtual Switch Logic
Switch
Purpose
Mode
Label
State Labels
Closed
Open
43
Not used
0 (disabled)
SWITCH_43
Closed
Open
143
Not used
0 (disabled)
SWITCH_43
Closed
Open
243
Not used
0 (disabled)
SWITCH_43
Closed
Open
Table 8-19. 700V-VF79-A-BE (V & F Protection with Reclosing) Virtual Output Logic
Output
Purpose
Description
Label
State Labels
Closed
Open
VOA
(OUTA)
Relay Trouble alarm, Alarm
Major, Alarm Minor
OUTA contact closes when
Relay Trouble, Major or
Minor alarm is TRUE
RELAY_TR
Active
Normal
BESTlogic expression: VOA= ALMMAJ+ALMMIN
VO1
(OUT1)
Not used
VO1
True
False
BESTlogic expression: VO1=0
VO1
(OUT1)
Not used
VO1
True
False
BESTlogic expression: VO1=0
VO2
(OUT2)
Breaker Trip Contact
initiated by Voltage and
Frequency Trips
OUT2 contact closes if any
voltage (24, 27P, 127P,
27X, 47, 59P, 159P, 59X,
159X) or frequency
(81
Y581) trip is TRUE.
V&F_BKR_
TR
Trip
Normal
BESTlogic expression: VO2=VO8
VO3
(OUT3)
Breaker Reclosing
OUT3 contact closes when
VO9 (25) or VO10 (25VM1)
is TRUE
BKR_CLOSE
Close
Normal
BESTlogic expression: VO3=79P+VO9+VO10
VO4
(OUT4)
Not used
VO4
True
False
BESTlogic expression: VO4=0