User programmable name setting command, Protection setting commands, User programmable name setting command -19 – Basler Electric BE1-700 User Manual
Page 265: Protection setting commands -19

SL-VO Command
Purpose:
Read/Set Output Logic
Syntax:
SL-VO[#[={Boolean equation}]]
Example:
SL-VO or SL-VO1=50TPT+50TNT+51PT+51NT+101T
Reference:
Section 7, BESTlogic Programmable Logic, Working With Programmable Logic
User Programmable Name Setting Command
SN Command
Purpose:
Read/Set User Programmable Names
Syntax:
SN[-{var}[={name},{TRUE label},{FALSE label}]
Example:
SN or SN-VO1=TRIP,CLOSED,OPEN or SN-IN1=BREAKER,OPEN,CLOSED
Reference:
Section 7, BESTlogic Programmable Logic, User Input and Output Logic Variable Names
Protection Setting Commands
S
Purpose:
Read all Protection settings
Syntax:
S{g} where g=setting group 0-1 or # for all groups
Example:
S# or S0 or S1
Reference:
Section 11, ASCII Command Interface, Settings (S) Command Descriptions
S
Purpose:
Read/Set 24 pickup level, time delay, reset delay and curve
Syntax:
S{g}-24[={pu(V/Hz)},{td},{rst},{crv}] where g=0,1
Example:
S0-24 or S0-24=2.5,6.5,9.9,2 or S1-24=3,2.0,5.0,1
Reference:
Section 4, Protection and Control, Voltage Protection
S
Purpose:
Read/Set 24 definite time pickup levels and time delays
Syntax:
S{g}-24D[={pu1(V/Hz)},{td1},{pu2(V/Hz)},{td2}] where g=0,1
Example:
S0-24D or S0-24D=1.1,6000,1.18,45000 or S1-24D=1.12,8000,1.20,60000
Reference:
Section 4, Protection and Control, Voltage Protection
S
Purpose:
Read/Set 25 delta volts, phase angle, slip freq and mode
Syntax:
S{g}-25[={Volts},{Ang},{Slip},{mode}] where g=0,1, mode=1-PF>XF, 0-PF<>XF
Example:
S0-25 or S0-25=5,3,0.1,0 or S1-27=2,5,0.25,1
Reference:
Section 4, Protection and Control, Synchronism-Check Protection
S
Purpose:
Read/Set 25VM live volts, dead volts, time delay, and VM1 logic
Syntax:
S{g}-25VM[={LV},{DV},{td},{VM1}] where g=0,1, VM1=DIS/123
Example:
S0-25VM or S0-25=80,20,100,123 S1-25VM=80,20,0.25,23
Reference:
Section 4, Protection and Control, Synchronism-Check Protection
S
Purpose:
Read/Set 27 pickup level, time delay, and inhibit level
Syntax:
S{g}-{x}27{p}[={pu(V)},{td(m)},{inh(V)}] where x= blank/1, g=0,1, p=P,X
Example:
S0-27P or S0-27P=100,10s,20, S0-27X=100,10s,20, S0-127P=80,5s,20
Reference:
Section 4, Protection and Control, Voltage Protection
9376700990 Rev M
BE1-700 ASCII Command Interface
11-19