Basler Electric BE1-700 User Manual
Page 209

Function
Purpose
BESTlogic
Expression
Mode Setting
27P
Used for phase undervoltage protection Level 1
0
1 (1 of 3)
127P
Used for phase undervoltage protection Level 2
0
1 (1 of 3)
27X
Not used
0
0
47
Used for negative-sequence voltage protection
0
1 (enabled)
59P
Used for phase overvoltage protection Level 1
0
1 (1 of 3)
159P
Used for phase overvoltage protection Level 2
0
1 (1 of 3)
59X
Used for 3Vo voltage detection Level 1
0
2
(3V0-3Ph VT Input)
159X
Used for 3Vo voltage detection Level 2
0
2
(3V0-3Ph VT Input)
62/162
Not used
0
0
79
Reclose Initiate: Initiates reclosing sequence when
RI is TRUE.
Breaker Status Logic: Closed breaker is indicated
when IN1 is de-energized.
Wait Logic: Stop recloser timing when timing for a
fault trip. TRUE when protection picked up
expression is TRUE.
Block/Drive to Lockout Logic: Drive recloser to
lockout when external recloser on/off switch is off.
Pilot Initiate: Initiate one high speed reclose when PI
is TRUE
VO14
/IN1
VO12
/IN2
VO13
1
(Power Up to Lockout)
81
Underfrequency Protection Level 1
0
1
(Phase VT Input)
281
Underfrequency Protection Level 1
0
1
(Phase VT Input)
381
Overfrequency Protection Level 2
0
1
(Phase VT Input)
481
Overfrequency Protection Level 1
0
1
(Phase VT Input)
581
Overfrequency Protection Level 2
0
1
(Phase VT Input)
9376700990 Rev M
BE1-700 Application
8-27