Table 8-7. 700C-OC79-A-BE (OC with 79) Function Block Logic
Function
Purpose
BESTlogic
Expression
Mode Setting
50TP
Block when recloser sequence controlled blocking output
is TRUE.
79SCB
1 (enabled)
50TN
Block when recloser sequence controlled blocking output
is TRUE or when disabled by IN4.
79SCB+/IN4
1 (3-ph residual)
50TQ
Block when recloser sequence controlled blocking output
is TRUE or when disabled by IN4.
79SCB+/IN4
1 (enabled)
150TP
Used for high set
0
1 (enabled)
150TN
Used for high set
0
1 (3-ph residual)
150TQ
Used for high set
0
1 (enabled)
51P
Used for phase TOC protection
0
1 (enabled)
51N
Used for neutral TOC protection. Disabled when IN4 is low
/IN4
1 (3-ph residual)
51Q
Used for negative-sequence TOC protection. Disabled
when IN4 is low
/IN4
1 (enabled)
151N
Not used
0
0 (disabled)
62
Not used
0
0 (disabled)
162
Not used
0
0 (disabled)
79
Reclose Initiate: Initiates reclosing sequence when RI is
TRUE.
VO8
1
(Power Up to
Lockout)
Breaker Status Logic: Closed breaker is indicated when
IN1 is de-energized.
Wait Logic: Stop recloser timing when timing for a fault
trip. TRUE when protection picked up expression is TRUE.
Block/Drive to Lockout Logic: Drive recloser to lockout
when external recloser on/off switch is off.
Pilot Initiate: Initiate one high speed reclose when PI is
TRUE
/IN1
VO12
VO9
0
BF
Not used
0
0 (disabled)
9376700990 Rev M
BE1-700 Application