Retrieving demand reporting information, Vt monitor functions (be1-700v), Retrieving demand reporting information -6 – Basler Electric BE1-700 User Manual
Page 138: Vt monitor functions (be1-700v) -6, Table 6-4. demand settings for current -6

Figure 6-3. Reporting and Alarms Screen, Demands Tab
Table 6-4. Demand Settings for Current
Setting
Range
Increment
Unit of
Measure
Default
Current Threshold Display Units
Sec. Amps, Pri. Amps, Per U
Amps, % Amps
N/A
Amps
Sec.
Amps
Current Threshold
.50 - 16.0 Sec. Amps
0.01
∗
0
Interval
0 - 60
1
Minutes
15
∗ Unit of measure is based on the threshold Display Units selection. The default is secondary amperes.
Retrieving Demand Reporting Information
Values and time stamps in the demand registers are reported in primary values. They can be read at the
front panel HMI and through the communication ports.
Today's Peak, Yesterday's Peak, and Peak Since Reset demand values are accessed through HMI
Screen 4.4, DEMAND REPORTS. Demand values viewed at the HMI can be reset by pressing the Reset
key. When the Reset key is pressed, the viewed register value is set to zero and then updated on the
next processing loop with the currently calculated demand value. No write access is needed to reset
demand register values at the HMI. It is also possible to preset a value into the Peak Since Demand
registers. This can be done by pressing the Edit key. Write access to the Reports functional area is
required to preset values at the HMI.
Values and time stamps in the demand registers can also be read through the communication ports by
using the RD (report demands) command.
Demand information specific to current can be obtained by including an object name with the command
function (R) and subgroup (D). Today's Peak, Yesterday's Peak and Peak Since reset information for
current is available using the RD-TI, RD-YI, and RD-PI commands.
VT MONITOR FUNCTIONS (BE1-700V)
The VT Monitor reporting function allows the user to enable or disable Fuse Loss Block Logic. Block
Phase, Block 3V0, and Block V2 and each be independently checked (enabled) or unchecked (disabled)
for the 27 and 59 elements. The default value for all of these logic functions is enabled.
6-6
BE1-700 Reporting and Alarm Functions