Basler Electric BE1-700 User Manual
Page 252

SG Command Example:
Example 1.
Obtain a report of all general settings.
>SG
SG-FREQ=60
SG-EMAIL1=0; SG-EMAIL2=0; SG-EMAIL3=0; SG-EMAIL4=0
SG-EMAIL5=0; SG-EMAIL6=0; SG-EMAIL7=0
SG-FREQ=60
SG-PHROT=ABC
SG-CTP=1
SG-CTG=1
SG-NOM= 0.0,5.00
SG-IN1= 4, 16; SG-IN2= 4, 16; SG-IN3= 4, 16; SG-IN4= 4, 16
SG-HOLDA=0; SG-HOLD1=1; SG-HOLD2=1; SG-HOLD3=0
SG-HOLD4=0; SG-HOLD5=1
SG-SGCON= 5
SG-DIP=15; SG-DIN= 1; SG-DIQ= 1
SG-LOG=15
SG-TARG=BF/50TP/150TP/50TN/150TN/50TQ/150TQ/51P/151P/62/162/51N/
151N/51Q,0
SG-TRIGGER=VO11,VO12,0
SG-OSC=16
SG-ID=BE1-700,SUBSTATION_1
SG-CLK=M,24,0
SG-SCREEN1=4.6; SG-SCREEN2=1.5.6; SG-SCREEN3=4.3.1; SG-SCREEN4=1.1
SG-SCREEN5=3.2; SG-SCREEN6=3.5; SG-SCREEN7=0; SG-SCREEN8=0
SG-SCREEN9=0; SG-SCREEN10=0; SG-SCREEN11=0; SG-SCREEN12=0
SG-SCREEN13=0; SG-SCREEN14=0; SG-SCREEN15=0; SG-SCREEN16=0
SG-COM0=9600,A0,P0,R1,X1
SG-COM2=9600,A0,P0,R1,X0,MF1,MPN,MR10,MS1,PW0
SN Command
Purpose:
Read/Set User Programmable Names
Syntax:
SN[-{var}[={name},{TRUE label},{FALSE label}]
Example:
SN or SN-VO1=TRIP,CLOSED,OPEN or SN-IN1=BREAKER,OPEN,CLOSED
SN Command Example:
Example 1.
Read the programmed labels for the alarm output (OUTA).
>SN-VOA
SN-VOA=VOA_LBL,TRUE,FALSE
S
Purpose:
Read all Protection settings
Syntax:
S{g} where g=setting group 0-1 or # for all groups
Example:
S# or S0 or S1
S
Example 1.
Obtain a list of settings for Setting Group 1.
>S1
S1-50TP=0.00, 0m,N
S1-50TN=0.00, 0m,N
S1-50TQ=0.00, 0m,N
S1-150TP=0.00, 0m,N
S1-150TN=0.00, 0m,N
S1-150TQ=0.00, 0m,N
S1-51P=0.00,0.0,V2,N
S1-51N=0.00,0.0,V2,N
11-6
BE1-700 ASCII Command Interface
9376700990 Rev M