Table 13-70. x43 mode 1 test commands -43, Table 13-71. x43 mode 1 on commands -43, Table 13-72. x43 mode 1 off commands -43 – Basler Electric BE1-700 User Manual
Page 339: Table 13-73. x43 mode 1 pulse commands -43
Table 13-70. x43 Mode 1 Test Commands
Command
Purpose
A=
Gains write access.
SL-N=NONE
Zero out custom logic settings. Overwrite with LOGIC=NONE settings.
Y
Confirm overwrite.
SL-N=MODE1
Sets MODE1 as custom logic name.
SL-43=1
Sets 43 for Mode 1 operation.
SL-VO1=43
Enables OUT1 operation.
EXIT;Y
Exit and save settings.
Step 2: Prepare to monitor the virtual switch operation. An ohmmeter or continuity tester may be used
to monitor the contact status of OUT1.
Step 3: Transmit the commands in Table 13-71 to the relay. These commands change the state of the
43 Switch to On. Result: OUT1 contact closes and remains closed.
Table 13-71. x43 Mode 1 On Commands
Command
Purpose
A=
Gains write access.
CS-43=1
Selects 43 for On operation.
CO-43=1
Executes 43 for On operation.
Step 4: Transmit the commands in Table 13-72 to the relay. These commands change the state of the
43 Switch to off. It is not necessary to gain access for the following steps unless the write
access timer expires. Result: OUT1 contact opens and remains open.
Table 13-72. x43 Mode 1 Off Commands
Command
Purpose
A=
Gains write access.
CS-43=0
Selects 43 for Off operation.
CO-43=0
Executes 43 for Off operation.
Step 5: Transmit the commands in Table 13-73. These commands pulse the 43 Switch on and off once.
Result: OUT1 contact closes for 200 milliseconds and returns to the open state.
Table 13-73. x43 Mode 1 Pulse Commands
Command
Purpose
A=
Gains write access.
CS-43=P
Selects 43 for Pulse operation.
CO-43=P
Executes 43 for Pulse operation.
Mode 2 - On/Off
Step 1: Prepare for Mode 2 testing by transmitting the commands in Table 13-74to the relay.
9376700990 Rev M
BE1-700 Testing and Maintenance
13-43