Basler Electric BE1-700 User Manual
Page 261

SG-CLK Command
Purpose:
Read/Program format of date and time display
Syntax:
SG-CLK[={date format(M/D)},{time format(12/24)},{dst enable(0/1)}]
Example:
SG-CLK=D,12,1 or SG-CLK=M,24,0
Reference:
Section 6, Reporting and Alarm Functions, Clock
SG-COM Command
Purpose:
Read/Set serial communications protocol
Syntax:
SG-COM[#[={baud},A{addr},P{pglen},R{reply ack},X{XON ena}]]
Example:
SG-COM0=9600 or SG-COM0=9600,A0,P24,R1,X1
Reference:
Section 11, ASCII Command Interface, Settings (S) Command Descriptions, Configuring
the Serial Port Communication Protocol
SG-CT Command (BE1-700C only)
Purpose:
Read/Set Phase/Neutral CT ratio
Syntax:
SG-CT[t][={CTratio}] where t = P/G
Example:
SG-CTP=80 or CTG=400:5 or CTG=400/5
Reference:
Section 3, Input and Output Functions, Power System Inputs
SG-DI Command (BE1-700C only)
Purpose:
Read/Set P(IA/IB/IC), N and Q demand interval
Syntax:
SG-DI[p][={interval}] where p=P/N/Q, interval=0-60 (min)
Example:
SG-DI or SG-DIP=15 or SG-DIN=1
Reference:
Section 6, Reporting and Alarm Functions, Demand Functions
SG-DSP Command
Purpose:
Read analog signal dsp filter type
Syntax:
SG-DSP[P/N] F=fundamental
Example:
SG-DSP, SG-DSPP, SG-DSPN
Reference:
Section 6, Reporting and Alarm Functions, Demand Functions
SG-EMAIL Command
Purpose:
Read/Enter email logic
Syntax:
SG-EMAIL[#[={email logic}]] where #=1-7
Example:
SG-EMAIL1=VO1*VO2 or SG-EMAIL5=50TPT+50TPPU
Reference:
Section 15, BESTNet Communication, Unique ASCII Commands
SG-FREQ Command
Purpose:
Read/Enter power system Frequency
Syntax:
SG-FREQ[={freq(HZ)}]
Example:
SG-FREQ=60 or SG-FREQ=50
Reference:
Section 3, Input and Output Functions, Power System Inputs
SG-HOLD Command
Purpose:
Read/Program Output Hold operation
Syntax:
SG-HOLD[n][={1/0 hold ena}] where 1=TRUE, 0=FALSE
Example:
SG-HOLD or SG-HOLD1=1 or SG-HOLD2=0
Reference:
Section 3, Input and Output Functions, Outputs
SG-ID Command
Purpose:
Read/Set relay ID and station ID used in reports
Syntax:
SG-ID[={relayID(up to 30 char)},{StationID(up to 30 char)}]
Example:
SG-ID=448,SUBSTATION3 or SG-ID=GEN3, POWERPOINT_SUBSTATION
Reference:
Section 14, BESTCOMS Software, Setting the Relay
9376700990 Rev M
BE1-700 ASCII Command Interface
11-15