Automatic setting group change, Automatic setting group change -53, Table 13-95. 51p element pickup settings -53 – Basler Electric BE1-700 User Manual
Page 349

Automatic Setting Group Change
Purpose: To verify the operation of the automatic setting group change function.
Reference Commands: SL-GROUP, SG-SGCON, SP-GROUP, CS/CO-GROUP, SL-51, S
Automatic Change
Step 1: Connect a current source to Terminals D1 and D2 (A-phase input).
Step 2: Prepare the automatic setting group change function for testing by transmitting the commands
in Table 13-94 to the relay.
Table 13-94. Automatic Setting Group Change Function Test Commands
Command
Purpose
A=
Gains write access.
SL-N=NONE
Zero out custom logic settings. Overwrite with LOGIC=NONE
settings.
Y
Confirm overwrite.
SL-N=ASG
Name custom logic for this test.
SL-GROUP=1,43,143,INI
Sets logic mode to discrete selection with virtual switch and
contact input control.
SL-51P=1,0
Enables 51P, disables blocking.
SG-SGCON=1S
Sets SGC on-time at 1 seconds.
SL-VO1=SG1
Closes OUT1 when SG1 is active.
SG-CTP=1
Sets the phase CT ratio at 1.
SG-TRIGGER=51PT,51PPU,0
Enable 51PT to log and trigger fault recording.
SL-43=3
Enables 43 Switch OFF/momentary ON mode.
SL-143=3
Enables 143 Switch OFF/momentary ON mode.
SN-43=MAN_SEL,GRP0,NORMAL
Assigns 43 Switch labels.
SN-143=MAN_SEL,GRP1,NORMAL Assigns 143 Switch labels.
SN-IN1=MAN_SEL,AUTO,MANUAL
Assigns IN1 Switch labels.
SP-GROUP1=1,75,1,70,51P
SG1 ts = 1 min @ 75%, tr = 1 min @ 70% of SG0 51P setting.
EXIT;Y
Exit and save settings.
Step 3: Select automatic setting group control by energizing Input IN1.
Step 4: Gain write access and transmit the appropriate setting commands in Table 13-95 to the relay.
Remember to save your setting changes with the EXIT;Y commands. An ohmmeter or
continuity tester may be used to monitor the output contacts (OUT1, OUT2, OUT3) status.
Table 13-95. 51P Element Pickup Settings
Sensing Type
Command
Comments
1 A
S0-51P=1.0,5.0,I2
pu = 1.0, td = 5, curve = I2
S0-51P=1.5,5.0,I2
pu = 1.5, td = 5, curve = I2
S0-51P=1.8,5.0,I2
pu = 1.8, td = 5, curve = I2
S0-51P=2.2,5.0,I2
pu = 2.2, td = 5, curve = I2
5 A
S0-51P=5.0,5.0,I2
pu = 5.0, td = 5, curve = I2
S0-51P=7.5,5.0,I2
pu = 7.5, td = 5, curve = I2
S0-51P=9.0,5.0,I2
pu = 9.0, td = 5, curve = I2
S0-51P=10.5,5.0,I2
pu = 10.5, td = 5, curve = I2
9376700990 Rev M
BE1-700 Testing and Maintenance