Basler Electric BE1-700 User Manual
Page 264

SL-51Q Command (BE1-700C only)
Purpose:
Read/Set Logic for 51Q Function Modules
Syntax:
SL-51Q[={mode},{BLK logic}]
Example:
SL-51Q or SL-51Q=1,0 or SL-51Q=1,IN3
Reference:
Section 4, Protection and Control, Overcurrent Protection
SL-101 Command
Purpose:
Read/Set Logic for Virtual Breaker switch (101)
Syntax:
SL-101[=mode] where mode=0/1 (disabled/enabled)
Example:
SL-101 or SL-101=0 or SL-101=1
Reference:
Section 4, Protection and Control, Virtual Switches
SL-59 Command (BE1-700V only)
Purpose:
Read/Set Logic for 59 Function Modules
Syntax:
SL-59[{p}[={mode},{BLK logic}]] where p=P/X
Example:
SL-59 or SL-59P=1,0 or SL-59X=2,0 or SL-159X=1,IN3
Reference:
Section 4, Protection and Control, Voltage Protection
SL-62 Command
Purpose:
Read/Set Logic for 62 Function Modules
Syntax:
SL-{x}62[={mode},{INI logic},{BLK logic}] where x=blank/1
Example:
SL-62 or SL-62=1,VO10,0 or SL-162=2,VO9,VO8
Reference:
Section 4, Protection and Control, General Purpose Logic Timers
SL-79 Command (Optional)
Purpose:
Read/Set for 79 Function
Syntax:
SL-79[={mode},{RILogic},{STATUSLogic},{WAITLogic},{LOCKOUTLogic},{PILOTLogic}]
Example:
SL-79 or SL-79=1,VO1+IN4,/IN1,IN2,IN3
Reference:
Section 4, Protection and Control, Reclosing
SL-81 Command (BE1-700V only)
Purpose:
Read/Set Logic for 81 Function Modules
Syntax:
SL-{x}81[={mode},{BLK logic}] where mode=0/1/X, x=blank/1/2/3/4/5
Example:
SL-81 or SL-81=1,0 or SL-81=X,0 or SL-181=1,IN3
Reference:
Section 4, Protection and Control, Frequency Protection
SL-BF Command (BE1-700C only)
Purpose:
Read/Set Logic for Breaker Failure Function Modules
Syntax:
SL-BF[{p}[={mode},{INI logic},{BLK logic}]]
Example:
SL-BF or SL-BF=1,VO1,0 or SL-BF=1,VO1,IN1
Reference:
Section 4, Protection and Control, Breaker Failure Protection
SL-GROUP Command
Purpose:
Read/Set Logic for Setting Group Module
Syntax:
SL-GROUP[={mode},{D0Logic},{D1Logic},{AUTOlogic}]
Example:
SL-GROUP or SL-GROUP=1,0,IN3,0
Reference:
Section 4, Protection and Control, Setting Groups
SL-N Command
Purpose:
Read/Set Name of the custom logic
Syntax:
SL-N[={name}]
Example:
SL-N=700TEST
Reference:
Section 7, BESTlogic Programmable Logic, Logic Schemes
11-18
BE1-700 ASCII Command Interface
9376700990 Rev M