beautypg.com

Section 18 – hardware multiplier module, 1 – hardware multiplier organization, 2 – hardware multiplier controls – Maxim Integrated DS4830A Optical Microcontroller User Manual

Page 148: Multiplier

background image

DS4830A User’s Guide

148

SECTION 18 – HARDWARE MULTIPLIER MODULE

The hardware multiplier module can be used by the DS4830A to support high-speed multiplications. The hardware
multiplier module is equipped with two 16-bit operand registers, a 32-bit read-only result register, and an accumulator
of 48-bit width. The multiplier can complete a 16-bit x 16-bit multiply-and-accumulate/subtract operation in a single
cycle. The hardware multiplier module supports the following operations without interfering with the normal core
functions:

o

Signed or unsigned Multiply (16 bit x 16 bit)

o

Signed or unsigned Multiply-Accumulate (16 bit x 16 bit)

o

Signed or unsigned Multiply-Subtract (16 bit x 16 bit)

o

Signed Multiply and Negate (16 bit x 16 bit)

18.1 – Hardware Multiplier Organization

The hardware multiplier consists of two 16-bit, parallel-load operand registers (MA, MB); a read-only result register
formed by two parallel 16-bit registers (MC1R and MC0R); an accumulator, which is formed by three 16-bit parallel
registers (MC2, MC1, and MC0); and a status/control register (MCNT). Figure 18-1 shows a block diagram of the
hardware multiplier.

Figure 18-1: Multiplier Organization

18.2 – Hardware Multiplier Controls

The selection of operation to be performed by the multiplier is determined by four control bits in the MCNT register:
SUS, MSUB, MMAC, and SQU. The number of operands that must be loaded to trigger the specified operation is
dictated by the OPCS bit setting, except when the square function is enabled (SQU = 1). Enabling the square
function implicitly defines that only a single operand (either MA or MB) needs to be loaded to trigger the square
operation, independent of the OPCS bit setting. The MCNT register bits must be configured to select the desired
operation and operand count prior to loading the operand(s) to trigger the multiplier operation. Any write to MCNT
automatically resets the operand load counter of the multiplier, but does not affect the operand registers, unless such
action is requested using the Clear Data Registers (CLD) control bit. Once the desired operation has been specified

MA

MB

MC0

MC1

MC2

MULTIPLIER

0

0

15

15

0

15

0

15

0

15

MCNT

Overflow

SUS
MMAC

OPCS

SQU

MSUB

CLD
MCW

MC0R

MC1R

0

15

0

15