beautypg.com

Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual

Page 554

background image

C-6

Logic Status Word

7000L-UM300I-EN-P – June 2013

7000 “C” Frame


Product Specific Logic Command – Firmware 3.001 and 3.002

To be used with gateway adapters such as RIO or DeviceNet.

Bit

Function

Value

Description

Notes

0

Stop

1

Stop Drive using Stop Profile

1

Start (Pulsed)

1

Start Drive on rising edge using Start
Profile

2

Jog

1

Jog at default or Preset Speed

3

Clear Faults

1

Clear most recent Fault in Queue

4

Clear Warnings

1

Clear most recent Warning in Queue

5

Clear Queues

1

Clear both Fault and Warning Queues

6

Direction

0

Forward

1

Reverse

7

Disable Reverse

1

Disable Reverse Direction (Maintained)

Done in Logic Parser

8

DPI Local/Remote
Profile

0

Remote

All adapters can control the drive
(Full multiplexed control)

1

Local

Only the adapter that has been
granted permission has control of
the Drive (Includes XIO Front

Panel Selector Switch)

10,9

Synchronous Transfer

0 0

No Command

0 1

Transfer to Line

1 0

Transfer to Drive

1 1

Illegal

11

Start Profile

0

Accel 1 (Default)

Must be maintained until at
Speed.

1

Accel 2

12

Stop Profile

0

Decel 1 (Default)

Must be maintained until drive
stopped.

1

Decel 2

15-13

Speed Command Select

0 0 0

No Command

0 0 1

External Ref0 ( Front Panel Pot)

0 1 0

Preset 1

0 1 1

Preset 2

1 0 0

Preset 3

1 0 1

External Ref1 (Programmed Reference)

1 1 0

Manual Reference (Local DPI Adapter)

1 1 1

Not Used