Logic Status Word
7000L-UM300I-EN-P – June 2013
7000 “C” Frame
Product Specific Logic Command – Firmware 3.001 and 3.002
To be used with gateway adapters such as RIO or DeviceNet.
Bit
Function
Value
Description
Notes
0
Stop
1
Stop Drive using Stop Profile
1
Start (Pulsed)
1
Start Drive on rising edge using Start
Profile
2
Jog
1
Jog at default or Preset Speed
3
Clear Faults
1
Clear most recent Fault in Queue
4
Clear Warnings
1
Clear most recent Warning in Queue
5
Clear Queues
1
Clear both Fault and Warning Queues
6
Direction
0
Forward
1
Reverse
7
Disable Reverse
1
Disable Reverse Direction (Maintained)
Done in Logic Parser
8
DPI Local/Remote
Profile
0
Remote
All adapters can control the drive
(Full multiplexed control)
1
Local
Only the adapter that has been
granted permission has control of
the Drive (Includes XIO Front
Panel Selector Switch)
10,9
Synchronous Transfer
0 0
No Command
0 1
Transfer to Line
1 0
Transfer to Drive
1 1
Illegal
11
Start Profile
0
Accel 1 (Default)
Must be maintained until at
Speed.
1
Accel 2
12
Stop Profile
0
Decel 1 (Default)
Must be maintained until drive
stopped.
1
Decel 2
15-13
Speed Command Select
0 0 0
No Command
0 0 1
External Ref0 ( Front Panel Pot)
0 1 0
Preset 1
0 1 1
Preset 2
1 0 0
Preset 3
1 0 1
External Ref1 (Programmed Reference)
1 1 0
Manual Reference (Local DPI Adapter)
1 1 1
Not Used