Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual
Page 391
Component Definition and Maintenance 6-47
7000 “C” Frame
7000L-UM300I-EN-P – June 2013
Test points description
TP1 – SCR gate output (attach oscilloscope between TP1 and TP2
to see gating pulses)
TP2 – SCR cathode output
TP3 – Common reference point for all other test point measurements,
except for TP1, which uses TP2 as its reference point
TP4 – The positive 20 V rail used for the SPGDB operation
TP5 – The positive 5 V rail used for the SPGDB operation
TP6 – The sense voltage taken from the sense resistor across the
SCR being controlled
TP7 – Trigger signal, which remains active for a fixed period of
time after the SCR being controlled, has turned on and the
voltage across it has collapsed
TP8 – Internal gating signal that indirectly turns on the SCR that is
being controlled
TP9 – Gating signal received from the commanding drive control
board, through the appropriate fiber optic cable
The yellow LED (LED 1) on the SGPDB indicates that the SCR
being controlled has a gating current flowing which is used to turn
the SCR on.
Test power connection
Fiber optic transmitter
and receiver
Thermal sensing
connection
TP9
TP8
TP7
TP6
TP3
TP4
TP5
Gate and cathode
thyristor connection
LED
Snubber connection
TP1
TP2
Test power connection
Fiber optic transmitter
and receiver
Thermal sensing
connection
TP9
TP8
TP7
TP6
TP3
TP4
TP5
Gate and cathode
thyristor connection
LED
Snubber connection
TP1
TP2
Figure 6.37 – Self-Powered Gate Driver Board