beautypg.com

Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual

Page 250

background image

Commissioning 4-45

7000 “C” Frame

7000L-UM300I-EN-P – Juen 2013

Plug 1 (P1) – INPUT

Terminal Numbers

Description

Value

1  2

Input Power (+56 V)

Plug 2 (P2) – CONTROL

Terminal Numbers

Description

Value

1  2

XIO PWR (+24 V 0.3 A) XIOCOMM ±5%

Plug 3 (P3) – SPGDB

Terminal Numbers

Description

Value

1  3

SPGDBPWR (+15 V 1 A) SPGDBCOMM ±5%

Plug 5 (P5) – SCLB

Terminal Numbers

Description

Value

1  2

+ LEMPWR (+24 V 1 A)  LCOMM ±1%

3  2

- LEMPWR (-24 V 1 A)  LCOMM ±1%

4  5

+15 V PWR (+15 V 1 A)  ACOMM ±3%

6  5

-15 V PWR (-15 V 1 A)  ACOMM ±3%

7  8

+5 V PWR (+5 V 1 A)  DGND (5.3 – 5.4)

9  10

+15 V ENC (+15 V 1 A)  ENC CONN ±1%

Plug 6 (P6) – SCMB

Terminal Numbers

Description

Value

1  2

+ LEMPWR (+24 V 1 A)  LCOMM ±1%

3  2

- LEMPWR (-24 V 1 A)  LCOMM ±1%

4  5

+15 V PWR (+15 V 1 A)  ACOMM ±3%

6  5

-15 V PWR (-15 V 1 A)  ACOMM ±3%

7  8

+5 V PWR (+5 V 1 A)  DGND (5.3 – 5.4)

9  10

+15 V ENC (+15 V 1 A)  ENC CONN ±1%

Plug 7 (P7) – CIB

Terminal Numbers

Description

Value

1  2

XIO PWR (+24 V 0.3 A) XIOCOMM ±5%

3  4

+15 V PWR (+15 V 1 A)  ACOMM ±3%

5  4

-15 V PWR (-15 V 1 A)  ACOMM ±3%

6  7

+5 V PWR (+5 V 0.1 A)  DGND (5.3 – 5.4)

8  9

+SCNPWR (+12 V 0.1 A) SCNCOMM ±1%