beautypg.com

Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual

Page 392

background image

6-48

Component Definition and Maintenance

7000L-UM300I-EN-P – June 2013

7000 “C” Frame

Terminal/connections description


TB1-1 – Connection to SCR snubber circuit used to extract energy

from the snubber for SPGDB operation

TB1-2 – Connection to SCR sensing resistor which indicates

conduction status of SCR being operated

TB2-1 – Positive 20V power supply connection to temperature

sensor board. Provides power to temperature sensor board.

TB2-2 – Common connection of positive 20V power supply to

temperature sensor board

TB3-1 – Positive 15V power supply connection for test power

used when commissioning drive or testing SPGDB

TB3-2 – Provides artificial sense voltage signal to allow SPGDB

to gate the SCR when in test mode. When the appropriate
test power cable is used, P/N 81001-262-51, this input is
shorted to TB3-1 to obtain the sense voltage.

TB3-3 – Common connection of positive 15V power supply used

for test power

TB4-2 – Cathode connection to SCR being controlled

TB4-1 – Gate connection to SCR being controlled

OP1

Blue fiber optic cable receptacle – Firing pulse command
from the processor

OT1

Grey fiber optic cable receptacle – Diagnostic status of
the SCR