Annual maintenance (cont.) – Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual
Page 480
6-136
Component Definition and Maintenance
7000L-UM300I-EN-P – June 2013
7000 “C” Frame
Clean all contaminated components using a vacuum cleaner
(DO NOT use a blower), and wipe clean components where
appropriate.
Check for coolant leak at all connections, visually and by touch
wherever possible.
Carry out the physical inspection and verification for the
proper operation of the contactor/isolator interlocks, and
door interlocks.
Carry out the physical inspection and verification for the proper
operation of the key interlocks.
Physical verification of the additional cooling fans mounted in
the AC Line Reactor cabinet, Harmonic Filter cabinet for
mounting and connections.
Carry out the cleaning of the fans and ensure that the ventilation
passages are not blocked and the impellers are freely rotating
without any obstruction.
Carry out the insulation meggering of the drive, motor, isolation
transformer/line reactor, and the associated cabling.
Refer to User Manual, Chapter 6 – Component Definition and
Maintenance for meggering procedure.
Check clamp head indicator washers for proper clamp pressure,
and adjust as necessary.
Refer to User Manual, Chapter 6 – Component Definition
and Maintenance for details on proper clamp pressure.