Logic Status Word

7000L-UM300I-EN-P – June 2013

7000 “C” Frame


Drive Logic Command Word – Database 3.001 and later

The following is the Logic Command from the output of the Parser.

It is a READ only variable in the Drive.

Bit

Function

Value

Description

Notes

0

Stop Command

0

Stop

1

Start Command (pulsed)

1

Start on Rising Edge only

2

Jog

1

Jog at preset speed

3

Clear Fault Queue

1

Clear Fault Queue

4

Clear Warning Queue

1

Clear Warning Queue

5

Drive Reset

1

Reset All Alarms (Faults and Warnings)

6

Direction

1

Reverse Rotation

0

Forward Rotation.

7

Start Profile

0

Accel 1 (Default)

Must be maintained until at
Speed.

1

Accel 2

8

Stop Profile

0

Decel 1 (Default)

Must be maintained until Drive
stopped.

1

Decel 2

10,9

Not Used

12,11

Synchronization

0 0

No command

0 1

Transfer to Line (Bypass)

1 0

Transfer to Motor

1 1

Illegal. Ignore this command

13

Force Stop

1

Force a Stop to the Drive

DPI Forced on Network Errors

14

Force Fault

1

Force a Class2 Fault in the Drive

DPI Forced on Network Errors

15

Not Used