Grounding Practices

The purpose of grounding is to:

• provide for the safety of personnel

• limit dangerous voltages on exposed parts with respect to ground

• facilitate proper over current device operation under ground fault

conditions, and

• provide for electrical interference suppression

I M P O R T A N T

I M P O R T A N T

Generally, the means used for external
grounding of equipment should be in accordance
with the Canadian Electrical Code (CEC), C22.1
or the National Electrical Code (NEC), NFPA
70 and applicable local codes.


Refer to the grounding diagrams that follow for ground connections.
The drive’s main ground bus must be connected to the system
ground. This ground bus is the common ground point for all grounds
internal to the drive.

ISOLATION

TRANSFORMER

AC

MOTOR

U (T1)

V (T2)

W (T3)

2U

2V

2W

GROUND BUS

Connected to the neutral point
of the output capacitor

OUTPUT

GROUND

NETWORK

ISOLATION

TRANSFORMER

AC

MOTOR

U (T1)

V (T2)

W (T3)

2U

2V

2W

GROUND BUS

Connected to the neutral point
of the output capacitor

OUTPUT

GROUND

NETWORK

Figure 2.21 – Ground Connection Diagram with Isolation Transformer



AC

MOTOR

U (T1)

V (T2)

W (T3)

2U

2V

2W

GROUND BUS

AC
REACTOR

TRANSFORMER

Connected to the neutral point
of the output capacitor

GROUND

FILTER

AC

MOTOR

U (T1)

V (T2)

W (T3)

2U

2V

2W

GROUND BUS

AC
REACTOR

TRANSFORMER

Connected to the neutral point
of the output capacitor

GROUND

FILTER

Figure 2.22 – Ground Connection Diagram with Line Reactor