Specifications – Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual
Page 28

1-10
Overview of Drive
7000L-UM300I-EN-P – June 2013
7000 “C” Frame
Specifications
Description
NEMA
IEC
Power Rating (Liquid Cooled)
3000-9000 hp
2240-6715 kW
Motor Type
Induction or Synchronous
Input Voltage Rating
3300V , 4160V, 6600V, 6900V
Input Voltage Tolerance
± 10% of Nominal
Voltage Sag
-30%
Power Loss Ride-Through
5 Cycles (Std)
> 5 Cycles (Optional UPS)
Input Protection
Metal Oxide Varistor (MOV)
Input Frequency
50/60 Hz, +/- 5%
Input Short-circuit Current Withstand
5 Cycle
3300 V – 6000 V
25 MVA RMS SYM
Basic Impulse Level
50 kV (0 – 1000 m)
Power Bus Design
Copper – Tin plated
Ground Bus
Copper – Tin plated 6 x 51 mm (¼ x 2 in.)
Customer Control Wire Way
Separate and Isolated
Input Power Circuit Protection
Vacuum Contactor with Fused Isolating Switch
or
Circuit Breaker
Input Impedance Device
Isolation Transformer or AC Line Reactor
Output Voltage
0 – 3300 V
0 – 4160 V
0 – 6600 V
0 – 6900 V
Inverter Design
PWM
Inverter Switch
Symmetrical Gate Commutated Thyristor (SGCT)
Inverter Switch Failure Mode
Non-rupture, Non-arc
Inverter Switch Failure Rate (FIT)
100 per 1 Billion Hours Operation
Inverter Switch Cooling
Double Sided, Low Thermal Stress
Inverter Switching Frequency
420-540 Hz
Number of Inverter SGCTs
Voltage
SGCTs (per phase)
3300/4160 V
6600/6900 V
4
6
SGCT PIV Rating
(Peak Inverse Voltage)
Voltage
PIV
3300/4160 V
6600/6900 V
6500 V
6500 V
Rectifier Designs
18 Pulse
PWM (Active Front End)
Rectifier Switch
SCR (18 Pulse), SGCT (PWM Rectifier)
Rectifier Switch Failure Mode
Non-rupture, Non-arc
Rectifier Switch Failure Rate (FIT)
100 per 1 Billion Hours Operation
Rectifier Switch Cooling
Double Sided, Low Thermal Stress
Number of Rectifier Devices per phase
Voltage
18-Pulse
PWM
3300 V
4160 V
6600 V
6
6
6
4
4
6
SCR PIV Rating
(Peak Inverse Voltage)
Voltage
18-Pulse
PWM
3300 V
4160 V
6600 V
4500 V
4500 V
6500 V
6500 V
6500 V
6500 V
Output Waveform to Motor
Sinusoidal Current / Voltage
Medium Voltage Isolation
Fiber Optic
Modulation techniques
SHE (Selective Harmonic Elimination)
PWM (Pulse Width Modulation)
For 3300V designs, contact factory.
Short-circuit fault rating based on input protection device (contactor or circuit breaker)
BIL derating based on altitudes < 1000 m (3,300 ft.) Refer to factory for derating.