6-88

Component Definition and Maintenance

7000L-UM300I-EN-P – June 2013

7000 “C” Frame


LED STATUS

CONDITION

Solid Green

Application Firmware Running

Flashing Green @ 0.25 Hz

Download Mode

Flashing Green @ 0.50 Hz

Download Mode – Currently being Programmed

Flashing Green @ 1.0 Hz

Ready

Flashing Green @ 2.0 Hz

Testing Flash Memory

1 Green Pulse

Waiting for Release upon Startup

2 Green Pulses

DCB-L – Waiting for DCB-M Status

3 Green Pulses

DCB-L – Waiting for CIB Status

10 Green Pulses

Tests Passed

Off

DCB in Test Mode

Solid Red

POST Failure – DSP

Flashing Red @ 0.25 Hz

Waiting for CIB

Flashing Red @ 0.50 Hz

Waiting for DCB

Flashing Red @ 1.0 Hz

Waiting for Adjacent Board

2 Red Pulses

POST failure - RAM

3 Red Pulses

POST failure – NVRAM

4 Red Pulses

POST failure – DPRAM

5 Red Pulses

POST failure – Application Flash

6 Red Pulses

POST failure – Text Flash

7 Red Pulses

POST failure – External DPRAM

8 Red Pulses

Failed FPGA Loading

9 Red Pulses

POST failure – USART – 1 Green Flash = Port 1
POST failure – USART – 2 Green Flashes = Port 2

10 Red Pulses

Returned from Application and Halted

11 Red Pulses

Programming Error - CRC

12 Red Pulses

Programming Error – Connection

13 Red Pulses

Programming Error – Feedback

14 Red Pulses

Programming Error – Overflow

There is also a healthy LED labeled D2 on each DCB. This LED is
an indication of several things, including a healthy watchdog
between the adjacent board, and healthy DC voltages. The light will
go out if either of the DC voltages (except the 5V) drops too low, or
if the watchdog is absent for 10 consecutive samples. The watchdog
is annunciated every 1 ms. The DCB OK contact on the SCB
operates in parallel to the D2 LED. When D2 is on, DCB OK is
closed.