beautypg.com

Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual

Page 29

background image

Overview of Drive 1-11

7000 “C” Frame

7000L-UM300I-EN-P – June 2013

Description

NEMA

IEC

Control Method

Digital Sensorless Direct Vector

Full Vector Control with Tach Feedback (Optional)

Tuning Method

Auto Tuning via Setup Wizard

Speed Regulator Bandwidth

5-25 Radians / Second

Torque Regulator Bandwidth

15-50 Radians / Second

Speed Regulation

0.1% without Tachometer Feedback

0.01 – 0.02% with Tachometer Feedback

Acceleration/Deceleration Range

Independent Accel/Decel – 4 x 30 sec.

Acceleration/Deceleration Ramp Rates

4 x Independent Accel/Decel

S Ramp Rate

Independent Accel/Decel – 2 x 999 sec.

Critical Speed Avoidance

3 x Independent with Adjustable bandwidth

Stall Protection

Delay / Speed

Load Loss Detection

Adjustable level, delay, speed set points

Control Mode

Speed or Torque

Current Limit

Adjustable in Motoring and Regenerative

Output Frequency Range

0.2-75 Hz

Service Duty Rating

Normal Duty

Heavy Duty

110% Overload for 1

minute every 10 minutes

(Variable Torque Load)

Contact Factory

Typical VFD Efficiency

> 98% (18 Pulse)

> 97.5% (PWM)

Contact Factory for Guaranteed Efficiency of

Specific Drive Rating

Input Power Factor

PWM Rectifier

18-Pulse Rectifier

with PFCC

0.98 Minimum,
30-100% Load

0.90-0.95,

12.5-100% Load

Meet IEEE 519 Harmonic Guidelines?

Yes

VFD Noise Level

< 85 dB(A) per OSHA Standard 3074

Regenerative Braking Capability

Inherent – No Additional Hardware or Software Required

Flying Start Capability

Yes – Able to Start into and Control a Spinning Load in

Forward or Reverse Direction

Operator Interface

40-character, 16-line formatted text

0.1 Hz Display speed resolution

Languages

English

Russian

Spanish

Chinese

French

Control Power

208-575 V, 3 Phase, 50/60 Hz

External I/O

16 Digital Inputs, 16 Digital Outputs

External Input Ratings

50-60 Hz AC or DC

120-240 V – 1 mA

External Output Ratings

50-60 Hz AC or DC

30-260 V – 1 Amp

Analog Inputs

(1) Isolated, (1) Non-isolated, 4-20 mA or 0-10 V

Analog Resolution

• Analog input 12 Bit (4-20 mA)

• Internal parameter 32 Bit resolution

• Serial Communication 16 Bit resolution ( .1 Hz)

(Digital Speed Reference)

Analog Outputs

(1) Isolated, (7) Non-isolated, 4-20 mA or 0-10 V

Communication Interface

SCANport /DPI

Scan Time

Internal SCANport – 10 ms

Internal DPI – 5 ms