Logic status word – database 3.001 and later – Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual
Page 553
Logic Status Word
C-5
7000 “C” Frame
7000L-UM300I-EN-P – June 2013
Logic Status Word – Database 3.001 and later
The following is the Logic Status word from the Drive.
It is common for all SCANport/DPI product specific peripherals.
Bit
Function
Value
Description
Notes
0
Ready
1
Drive is Ready
1
Running
1
Drive is Running
2
Commanded Direction
1
Drive has been commanded to run forward
0 = Reverse Command
3
Rotating Direction
1
Drive is rotating in the forward direction
0 = Reverse Rotation.
4
Accelerating
1
Drive is accelerating to commanded speed
0 = Drive is at speed
5
Decelerating
1
Drive is decelerating to commanded speed
0 = Drive is at speed or stopped
6
At Speed
1
Drive has reached the commanded speed
7
On Bypass
1
Motor is on bypass
0 = Motor connected to Drive
8
Reverse Enabled
1
The reverse command feature is enabled.
Changed in FRN 3.001 from
Reverse Disabled
9
Drive Fault
1
Drive has faulted
10
Drive Warning
1
Drive has encountered a warning
11
Local Lock
1
A DPI or XIO has local control of the drive
12
Forced Stop
1
A DPI adapter or CIB has forced the drive
to stop due to internal problems
15,13
Preset Speeds
0 0 0
External Reference 0 (Speed Pot)
0 0 1
External Reference 1 (Analog Input)
0 1 0
External Reference 2 (Current Loop Input)
0 1 1
Preset 1
1 0 0
Preset 2
1 0 1
Preset 3
1 1 0
Jog Preset
1 1 1
DPI Adapter Reference