beautypg.com

Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual

Page 116

background image

2-80

Drive Installation

7000L-UM300I-EN-P – June 2013

7000 “C” Frame

1.25” or 2.0” NPTF

Female Pipe Threads

Process Water Inlet

Process Water Outlet

Drive Coolant Inlet

Drive Coolant Outlet

Figure 2.20 – Pipe Flange Detail



Table 2.A – Customer Cooling Requirements for Liquid-to-Liquid Heat Exchangers

Drive

Min. Flow Rate

Max. Pressure

(psig)

Pressure Drop

(kPa)

Temperature ( °C)

Rectifier Voltage

Amps

US

Gpm

L/m

Min.

Max.

18-Pulse

4160

375

33.0

125

435

18

< 0

> 32

430

48.5

183

435

38

< 0

> 32

495

54.5

206

435

43

< 0

> 32

575

22.5

84

435

9

< 0

> 32

657

24.0

90

435

10

< 0

> 32

6600

375

19.5

72

435

7

< 0

> 32

430

21.5

80

435

8

< 0

> 32

495

26.5

100

435

13

< 0

> 32

575

29.0

109

435

15

< 0

> 32

657

37.5

142

435

25

< 0

> 32

PWM

4160

375

19.5

74

435

7

< 0

> 32

430

24.0

90

435

10

< 0

> 32

495

26.5

100

435

13

< 0

> 32

575

33.0

125

435

19

< 0

> 32

6600

375

37.0

139

435

24

< 0

> 32

430

44.5

167

435

34

< 0

> 32

495

48.5

184

435

40

< 0

> 32

575

54.5

206

435

43

< 0

> 32

NOTE:

US Gpm = Gallons per minute (U.S.)

L/m = Liters per minute