beautypg.com

Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual

Page 428

background image

6-84

Component Definition and Maintenance

7000L-UM300I-EN-P – June 2013

7000 “C” Frame

LEDs

Green operational LED on front of unit detects DC FAIL output.

 LED ON: outputs good

 LED OFF: outputs bad

Terminal/connections descriptions

P1-DC input

PIN#

LABEL

DESCRIPTION ONLY

1

+56V

+56V input

2

+56V COMM

+56V common

3

EARTH

earth ground

P2-CONTROL

PIN#

LABEL

DESCRIPTION ONLY

1

XIO_PWR (+24V,3A)

+24V,3A/com5

2

XIOCOMM (com5)

0V/com5

P3-SPGDB

PIN#

LABEL

DESCRIPTION ONLY

1

SPGDBPWR (+15V,1A)

+15V,1A/com4

2

SPGDBPWR (+15V,1A)

+15V,1A/com4

3

SPGDBCOMM (com4)

0V/com4

4

SPGDBCOMM (com4)

0V/com4

P4-CIB

PIN#

LABEL

1

DC FAIL

2

DC WARNING

3

SPGDBFAIL

4

DC/DCFAILCOMM

5

EARTH

P5-SCBL

PIN#

LABEL

DESCRIPTION ONLY

1

+LEMPWR (+24V,1A)

+24V,1A/com2

2

LCOMM (com2)

0V/com2

3

–LEMPWR (-24V,1A)

-24V,1A/com2

4

+15V_PWR (+15V,1A)

+15V,1A/com1

5

ACOMM (com1)

0V/com1

6

–15V_PWR (-15V,1A)

-15V,1A/com1

7

+5V_PWR (+5V,10A)

+5V,10A/com1

8

DGND (com1)

0V/com1

9

+15V_ENC (+15V,1A)

+15V,1A/com3

10

ENC_COMM (com3)

0V/com3

11

DGND (com1)

0V/com1