beautypg.com

Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual

Page 111

background image

Drive Installation 2-75

7000 “C” Frame

7000L-UM300I-EN-P – June 2013

Information regarding termination of customer cables


Customer termination assemblies can accommodate either top or
bottom customer cable entry. The assemblies as provided are for
bottom cable entry.

4-hole insulator

Bolts

Customer supplied lugs
4 lugs per phase maximum

M10 bus connection
hardware

Lug pad shown with
bottom cable entry
orientation

Figure 2.14 – Typical Line Cable Termination

(Assembled for Bottom Cable Entry)

For top line cable entry, it is necessary to remove the lug pads and
re-orient them as shown in Figure 2.15. To remove the lug pads,
disconnect the M10 bus connection hardware (17 mm hex tooling
required). Remove the two bolts that secure the lug pad to the 4-hole
insulator. See Appendix B for Torque Values of electrical connections.

Lug pad oriented
for top cable entry


Figure 2.15 – Typical Line Cable Terminal Assembly

(Modified for Top Cable Entry)