Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual
Page 504
7-20
Troubleshooting
7000L-UM300I-EN-P – June 2013
7000 “C” Frame
FAULT
MESSAGE
FAULT
CODE
DESCRIPTION
RECOMMENDED ACTIONS
OutPut Open
43
DO or OP open fault
– Drive sees DO or OP contactor open.
– Check for open circuit at the drive output
PD Capcty Lo
47
Parallel Drive Capacity Low.
This is applicable to parallel drive only
– The available drive capacity is less than
50% of the motor rated current. The
drive cannot run.
Pressure Loss
(C-Frame Only)
223
The measured system pressure has
dropped below a preset trip level. The
standard operating pressure is around
50psi. The pressure switch is not designed
to be an accurate measure of pressure, but
is designed as a Pressure/No Pressure
indication. Typically anything less than
20psi will activate this switch.
– Check that the pumps are operating
– Verify that there are no leaks in the
system
– Verify that there is no blockage in the
system
Printer USART
242
CIB Hardware Fault
– CIB Hardware Problem
– Cycle control Power to the drive, and if
the problem still exists the board should
be replaced
Pump/Fan Pwr Off
(C-Frame Only)
230
The control power to the pumping system
and the heat exchanger fans is not present.
– Verify the disconnect switch is closed
and that there are no blown fuses
– Measure the voltage at the pump and fan
inputs to ensure voltage is present
– Trace the feedback to the drive from the
circuit, looking for loose wiring or
incorrect auxiliaries
R Neutral OC
206
Neutral Resistor Over Current.
This is applicable to Direct to Drive only
– Check the neutral R for open
– Check devices on rectifier and inverter
for short circuits
– Check the Line and Motor Filter
Capacitors for short between Phase-to-
Neutral or Phase-to-Phase. Refer to
Chapter 6 of the User‟s Manual for
detailed instructions on Testing Filter
Capacitors.
Rect Heatsink FO
198
While Not Running, the Fiber Optic signal
from the TFB on the Rectifier Heatsink,
connected to Channel A fiber optic receiver
RX7 on FOI-L-A is not present. This is only
a fault while not running. If this occurs while
running it will appear as a warning.
– Check TFB and FOI board for power
Check the Fiber Optic cables are
properly seated in the transmitters and
receivers
– Check the fiber optic cable for
kinks/bends/breaks that could be
blocking the signal
Rect Temp ChB FO
199
Not Normally Used: While Not Running, the
Fiber Optic signal from the optional TFB
connected to Channel B fiber optic receiver
RX7 on FOI-L-B is not present. This is only
a fault while not running. If this occurs while
running it will appear as a warning.
Rec HS Low Temp
204
If the measured temperature RHeatsink
Temp C (P254) is less than 2°C, and the
drive is not running, the drive will display this
fault.
– Verify that the ambient in the control
room is not below 2°C
– Verify power to the TFB