beautypg.com

Specifications (cont.) – Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual

Page 30

background image

1-12

Overview of Drive

7000L-UM300I-EN-P – June 2013

7000 “C” Frame

Specifications (cont.)

Description

NEMA

IEC

Communication Protocol

RIO

Interbus

DeviceNet

Lonworks

ControlNet

Can Open

Ethernet

RS485 HVAC

Profibus

RS485 DF1

Modbus

RS232 DF1

Modbus +

RS232 C

Enclosure

NEMA 1/ 12 Force Vent

IEC IP21 / IP42

Lifting Device

Standard / Removable

Mounting Arrangement

Mounting Sill Channels

Structure Finish

Epoxy Powder – Paint

Exterior Sandtex Light Grey (RAL 7038) – Black (RAL 8022)

Internal – Control Sub Plates – High Gloss White (RAL 9003)

Interlocking

Key provision for customer input Disconnecting Device

Corrosion Protection

Unpainted Parts (Zinc Plates / Bronze Chromate)

Fiber Optic Interface

Rectifier – Inverter – Cabinet (Warning/Trip)

Door Filter

Painted Diffuser with Matted Filter Media

Door Filter Blockage

Air Flow Restriction Trip/Warning

Coolant

Iron and chloride free ethylene glycol

mixed with de-ionized water

Coolant Conductivity

1-2 micro-Siemens/CM

Heat Exchangers

Liquid to Air / Liquid to Liquid

Ambient Temperature

0° to 40°C (32°F to 104°F)

Storage and Transportation
Temperature Range

-40°C to 70°C (-40°F to 185°F)

Relative Humidity

95% Non-Condensing

Altitude (Standard)

0 to 3300 ft. (0 to 1000 m)

Altitude (Optional)

0 to 16400 ft. (1001 to 5000 m)

Seismic (UBC Rating)

1, 2, 3, 4

Standards

NEMA, IEC, CSA, UL, ANSI, IEEE