Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual
Page 164
3-42
Operator Interface
7000L-UM300I-EN-P – June 2013
7000 “C” Frame
Figure 3.49 – Analog Setup
This will begin the selection process of a tag as described in the
section entitled "Select a Parameter". When you have completed
the selection process, the selected tag will be assigned to the port.
To remove an assignment to the highlighted port, press the [delete]
(Backspace) key.
The changes made do not take affect until you press [F10] and exit
the screen. Any time prior to this you may cancel all of the changes
made after coming to the screen by pressing the [F7] key.
Fault Masks
A number of the faults within the drive may be selectively enabled
or disabled by you.
To view or modify the current fault mask
settings
, use
the up/down arrow keys on the SETUP screen to select
the 'Fault Masks' option and press the [enter] key.
A typical screen as shown in Figure 3.50 shows all of the user
maskable faults. Associated with each fault is the state of the mask.
If OFF, it means the fault is disabled and will not occur. The normal
state is ON or enabled.
To change the state of the mask, use the [cursor up] or [cursor down]
keys to select the desired fault and press the [enter] key. Each press
of the [enter] key will toggle the state of the mask as shown in
Figure 3.51. (If nothing happens, you do not have proper access to
the drive. Exit to the SETUP screen and refer to the section entitled
Enter/Modify an Access Level
to gain access).