Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual

Page 513

background image

Troubleshooting

7-29

7000 “C” Frame

7000L-UM300I-EN-P – June 2013

FAULT

MESSAGE

FAULT

CODE

DESCRIPTION

RECOMMENDED ACTIONS

2U1A Offline SC

378

6P or 18P SCR RECTIFIER FAULT

(Offline Short-Circuit)

For SCR rectifiers, this fault will occur after
the initial contact closure, or during the

diagnostic sequence after a start command.
This is the first test on the rectifier. When all

devices blocking, the feedback from the
devices should toggle from open to short to
open every time the line voltage sine wave

passes through zero. If this is consistently
showing short (no feedback), then the drive
assumes that the device is Short-Circuited.

– Complete a resistance check on the

rectifier, including the gate-cathode
resistance, the snubber and sharing
resistors

– Complete a firing check on the rectifier
– Verify the snubber circuitry, and the

sharing resistors

– Verify fiber optic integrity from SCRGD

board transmitter to FOI board receiver

– Replace all faulty components

2U1B Offline SC

384

2U1C Offline SC

408

2U4A Offline SC

381

2U4B Offline SC

387

2U4C Offline SC

411

2V3A Offline SC

380

2V3B Offline SC

386

2V3C Offline SC

410

2V6A Offline SC

383

2V6B Offline SC

389

2V6C Offline SC

413

2W2A Offline SC

379

2W2B Offline SC

385

2W2C Offline SC

409

2W5A Offline SC

382

2W5B Offline SC

388

2W5C Offline SC

412

3U1B Offline SC

450

3U4B Offline SC

453

3V3B Offline SC

452

3V6B Offline SC

455

3W2B Offline SC

451

3W5B Offline SC

454

4U1C Offline SC

456

4U4C Offline SC

459

4V3C Offline SC

458

4V6C Offline SC

461

4W2C Offline SC

457

4W5C Offline SC

460