4 master current, 5 external torque reduction, Master current – Lenze EDS4900U-REG User Manual
Page 95: External torque reduction, Configuration

Configuration
7-4
48XX/49XXSHB0399
JOG set-value enabling with control via keypad or LECOM interface
Active the JOG set-values under C045.
Code
Name
Possible settings
Lenze Selection
Info
C045
¤ JOG enable
0
-0-
Main set-value (C046) active
-1-
Set-value JOG1 active
...
-15-
Set-value JOG15 active
With terminal control only display
7.1.1.4
Master current
If the analog set-value is to be entered via X1/8 as master current, the current
setting range can be selected under C034:
( For -20mA...+20mA:
C034 = -0-
( For 4...20mA:
C034 = -1- (only unipolar)
If range 4...20mA is selected and the current is less than 2mA, the fault ”Sd5” is
indicated.
Spannungsleitwert auf Stromleitwert (Strombürde 250
W) mit dem Schalter S3/1
auf der Steuerbaugruppe 4902MP umschalten:
( Master voltage/potentiometer:
S3/1 = OFF
(Default setting)
( Master current:
S3/1 = ON
(see chapter 4.3.4)
7.1.1.5
External torque reduction
With a potentiometer, it is possible, for instance, to apply a voltage externally to
terminal 2. This voltage has a direct influence on the I
max
values set under C022
and C023.
Note!
A voltage of 0V at terminal X1/2 corresponds to I
max
if C005 = -1X-, -5X-, -6X- or
-72-.
The corresponding speed set-value is to be applied via terminal X1/8.
Alternatively to the set-value potentiometer, the current limitation can also be under
linear influence from an external control voltage.