3 fault messages, Fault messages, Troubleshooting and fault elimination – Lenze EDS4900U-REG User Manual
Page 249

Troubleshooting and fault elimination
8-4
48XX/49XXSHB0399
8.3
Fault messages
Note!
If the fault message is interrogated by a fieldbus, the fault message is represented
not by an abbreviation but a LECOM no. read from C167.
Display
Cause
Remedy
---
No fault
-
-
ACI
Armature circuit
interrupted
Defective fuse in the armature circuit or cable
interruption
Check armature fuse or remove cable
interruption
CCr
System fault
Strong interference on control cables
Ground or earth loops in the wiring
Screen control cables
Check PE wiring (see chapter 4.4”Installation
of a CE-typical drive system”)
CE0
Communication fault
(automation interface)
Interference during transmission of control
commands via the automation interface
Check wiring
CE9
Communication fault
(serial interface)
Faulty messages from the serial interface.
Check wiring
dEr
Motor blocked
High standstill torque or motor mechanically
blocked.
Remove motor blockage or increase blocking
time under C124 or blocking current under
C123.
EEr
External fault (TRIP-Set)
A digital input assigned to the TRIP-Set
function has been activated
Check external encoder.
Check polarity to activate TRIP set under
C118.
FCI
Field circuit interrupted
Defective field fuses F1 and F2 or
interrupted field circuit.
Replace field fuses when no voltage is applied
or remove cable interruption.
LF
Mains underfrequency
Mains frequency < 47Hz
Check mains frequency,
controller must only be driven within a
frequency range from 47 to 63 Hz.
LU
Undervoltage
Mains voltage < 340 V or 410 V
(Variant 500 V mains voltage)
Mains synchronisation has not detected any
voltage zero for more than 25 ms.
Increase electronics supply separately with a
connected transformer or
use a controller with a lower mains connection
voltage.
LU1
Phase failure
Failure of the mains voltage or mains
interruption
Check mains voltage and remove mains
interruption
Adapt mains synchronisation to mains
conditions under C237.
OC5
Controller overload
Frequent or excessive acceleration with
overcurrent
Permanent overload with I
A
> 1.05 I
Arated
Check drive dimensioning
OC6
Motor is thermally
overloaded
Motor is thermally overloaded by, for instance,
- impermissibly high continuous currents
- frequent and excessive
acceleration processes
Check drive dimensioning
OF
Mains overfrequency
Mains frequency > 63Hz
Check mains frequency
Controller must only be driven within a
frequency range from 47 to 63 Hz.
OH
Heat sink temperature is
higher than the value set
in the controller
Ambient temperature
T
amb
> 45
C or 35 C
Heat sink very dirty
Incorrect mounting position
Allow controller to cool and ensure better
ventilation
Check ambient temperature in the control
cabinet
Clean heat sink
Change mounting position
Show/Hide Bookmarks