1 mains fuses, Mains fuses, Accessories – Lenze EDS4900U-REG User Manual
Page 273: 1 mains fuses stop

Accessories
13-3
48XX/49XXSHB0399
13.1.1
Mains fuses
Stop!
An additional cable protection is required when using fuses of the operating class
aR (partial characteristic) as phase fuses.
If the fuses of the operating class gR also protect the cable, the cable cross-
sections must be dimensioned according to the fuse. Otherwise, provide a
separate cable protection!
Type
Max. perm. size of the phase fuse (F’1, F’2, F’3)
Mains voltage
$550V +0%
Fuse holder
Fuse type
Operating class
Order designation
Order designation
4902
FF 32 A
(22 x 58)
gR
EFSFF0320AYI
EFH30006
4903
FF 40 A
(22 x 58)
gR
EFSFF0400AYI
EFH30006
4904
FF 80 A
(22 x 58)
gR
EFSFF0800AYI
EFH30006
4905
FF 200 A
(01.110)
aR
EFSFF2000AYR
EFH10003
4906
FF 250 A
(01.110)
aR
EFSFF2500AYR
EFH10003
4907
FF 350 A
(01.110)
aR
EFSFF3500AYR
EFH10003
4X08
FF 450 A
(01.110)
aR
EFSFF4500AXP
EFH10003
4X09
FF 700 A
(02.110)
aR
EFSFF7000AYR
EFH10003
TAB 1
Assignment of max. mains fuse size to the controller
Type
Recommended phase fuse size (F’1, F’2, F’3) when I
Amax
= I
Arated
of the
controller
Fuse holder
controller
Mains voltage
$460V +0%
Fuse type
Operating class
Order designation
Order designation
4902
FF 20 A
(14 x 51)
aR
EFSFF0200AYH
EFH10002
4903
FF 32 A
(14 x 51)
aR
EFSFF0320AYH
EFH10002
4904
FF 63 A
(22 x 58)
aR
EFSFF0630AYI
EFH30006
4905
FF 125 A
(00.80)
aR
EFSFF1250AXL
EFZ0003
4906
FF 200 A
(00.80)
aR
EFSFF2000AXL
EFZ0003
4907
FF 315 A
(00.80)
aR
EFSFF3150AXL
EFZ0003
4X08
FF 400 A
(01.110)
aR
EFSFF4000AXR
EFH10003
4X09
FF 550 A
(01.110)
aR
EFSFF5500AXP
EFH10003
TAB 2
Assignment of mains fuses to the controller when I
Amax
= I
Arated
and a mains voltage of
$ 460V +0%
The controllers 4X11 to 4X13 are equipped with cell fuses (F1.1/F1.2, F2.1/F2.2,
F3.1/F3.2). Fuseholders are not necessary.